Parameter Description
15-10 Logging Source
Array [4]
Option:
[1627] Power Filtered [hp]
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1650] External Reference
[1652] Feedback [Unit]
[1654] Feedback 1 [Unit]
[1655] Feedback 2 [Unit]
[1656] Feedback 3 [Unit]
[1660] Digital Input
[1662] Analog Input 53
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
[1666] Digital Output [bin]
[1675] Analog In X30/11
[1676] Analog In X30/12
[1677] Analog Out X30/8 [mA]
[1690] Alarm Word
[1691] Alarm Word 2
[1692] Warning Word
[1693] Warning Word 2
[1694] Ext. Status Word
[1695] Ext. Status Word 2
[1830] Analog Input X42/1
[1831] Analog Input X42/3
[1832] Analog Input X42/5
[1833] Analog Out X42/7 [V]
[1834] Analog Out X42/9 [V]
[1835] Analog Out X42/11 [V]
[1850] Sensorless Readout [unit]
[3110] Bypass Status Word
15-11 Logging Interval
Range:
Size related
[
0.000 -
*
0.000 ]
15-12 Trigger Event
Option:
Function:
Selects the trigger event. When the
trigger event occurs, a window is
applied to freeze the log. The log will
then retain a specified percentage of
samples before the occurrence of the
trigger event (15-14 Samples Before
Trigger).
[0]
False
*
[1]
True
®
VLT
HVAC Drive Programming Guide
Function:
Function:
Enter the interval in milliseconds
between each sampling of the
variables to be logged.
®
MG.11.CC.02 - VLT
is a registered Danfoss trademark
15-12 Trigger Event
Option:
Function:
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[33] Digital input DI18
[34] Digital input DI19
[35] Digital input DI27
[36] Digital input DI29
[37] Digital input DI32
[38] Digital input DI33
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
15-13 Logging Mode
Option:
Function:
[0]
Log always
Select Log always [0] for continuous
*
logging.
[1]
Log once on
Select Log once on trigger [1] to
trigger
conditionally start and stop logging using
15-12 Trigger Event and 15-14 Samples
Before Trigger.
3
3
115