3.3.9 Access to Control Terminals 3.3.10 Basic Wiring Example 3.3.11 Electrical Installation, Control Cables 3.3.12 Electrical Installation - EMC Protection 3.3.13 Safety Earth Connection 3.3.14 Basic Examples of Control Connections ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 2
6.7 Parameters: 6-** Analog In/Out 6.8 Parameters: 7-** Controllers 6.9 Parameters: 8-** Communications and Options 6.10 Parameters: 13-** Smart Logic Control 6.11 Parameters: 14-** Special Functions 6.12 Parameters: 15-** Drive Information ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 3
CDS302 and CDS303 6.13 Parameters: 16-** Data Read-outs 6.14 Parameters: 25-** Cascade Controller 6.15 Parameters: 28-** Compressor Functions 6.16 Parameter Lists 6.16.1 Conversion 7 Troubleshooting 7.1.1 Warnings/Alarm Messages 8 General Specifications Index ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
1800 to 5400 RPM for CDS302 and 1500 to 6000 RPM for time of 12 s, with an interval between starts of 5 CDS303. minutes (300 s). The short cycle delay values are adjustable in parameter group 28-0* Short Cycle Protection. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
In case of a blocked rotor, the Compressor Drive trips with an alarm [A18] Start failed, if the speed fails to get above the minimum speed limit for the compressor within 2 s. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
15-43 Software Version. WARNING Table 2.1 Installation in high altitudes: CDS303 Operating Instructions Software version: 1.0x By altitudes above 2 km, please contact Danfoss regarding PELV. 2.1.2 Caution These Operating Instructions can be used for all CDS303 CAUTION ®...
) and for the specific unit. Stop Category 0 (as defined in EN 60204-1 Danfoss has named this functionality Safe Stop. Before 2.1.7 Leakage Current integration and use of Safe Stop in an installation, perform a thorough risk analysis to determine whether the Safe...
• a subsystem related to all failures. IEC 61800-5-2: 2007 – safe torque off (STO) IEC 61508 Safety Integrity Level function • IEC 62061: 2005 SIL CL2 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 9
180/p degrees. p denotes the pole pair number. • This function is suitable for performing mechanical work on the system or affected area of a machine only. It does not provide electrical ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 10
For all applications with Safe Stop it is important that short circuit in the wiring to T37 can be excluded. Exclude the short circuit as described in EN ISO 13849-2 D4 by the use of protected wiring (shielded or segregated). ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 11
Safety relay Emergency stop Frequency converter Table 2.5 [Reset] key Safety relay Emergency stop Table 2.7 Illustration 2.5 SS1 Example Frequency converter [Reset] key Safety relay Emergency stop Table 2.6 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 12
After activation of Safe Stop (that is, after the response time), the frequency converter coasts (stops creating a rotational field in the motor). The response time is typically less than 10 ms. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Relay W or [8] PTC 1 & Relay A/W): 2.1 Remove the 24 V DC voltage supply to terminal 37 by the interrupt device while the frequency converter drives the motor (that is ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Illustration 3.4 Frame Sizes C1 and C2, IP55/66/Type 1/Type 12 into account. 3.2 Mechanical Installation 61 68 39 42 3.2.1 Accessory Bags Find the following parts included in the CDS302 Accessory Illustration 3.5 Frame Size C3, IP20/Chassis ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Frequency converter sizes differ, but terminal numbers are always the same. Incoming power is always 91, 92, 93 labeled L1, L2, L3. Illustration 3.6 How to Connect to Mains and Earthing for B1 and B2 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 18
For correct cable dimensions see 8 General Specifications. Illustration 3.7 How to Connect to Mains and Earthing for B3 without RFI. Illustration 3.8 How to Connect to Mains and Earthing for B3 with RFI. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 19
Incoming power is always 91, 92, 93 labeled L1, L2, L3. Illustration 3.10 How to Connect to Mains and Earthing for C1 and C2. Illustration 3.9 How to Connect to Mains and Earthing for B4. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Fasten decoupling plate to the bottom of the frequency converter with screws and washers from the accessory bag. Attach motor compressor cable to terminals 96 (U), 97 (V), 98 (W). ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Illustration 3.17 C1, B1 and B2 Enclosures • The frequency converter makes through an Electronic current measurement anti-overload and 10 pole plug digital I/O 3 pole plug RS485 Bus ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Illustration 3.22 Connect terminals 18, 27 and 37 to +24 V Illustration 3.19 (terminal 12/13) Default settings: To remove the cable from the terminal: 18 = start 27 = coast inverse ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 23
® How to Install Operating Instructions VLT CDS302 and CDS303 Start Stop inverse Safe Stop Speed Start (18) Start (27) Illustration 3.23 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 25
If very long control cables are used, 50/60 Hz earth loops Illustration 3.26 may occur. Solve this problem by connecting one end of the screen to earth via a 100 nF capacitor (keeping leads short). ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
The EMC performance of flexible conduits varies a the paragraph. lot and information from the manufacturer must be obtained. • Connect the screen/armour/conduit to earth at both ends for motor compressor cables as well as ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
3.5 mA. To ensure a good mechanical connection from the earth cable to the earth connection (terminal 95), the cable cross-section must be at least 10 or 2 rated earth wires terminated separately. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Controls using an external controller with 4-20 mA signal. Change switch 53 from U to I. It is not necessary to change any parameters, as this is the default value. Illustration 3.29 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
NOTE The recommendations given do not provide UL branch circuit protection. Danfoss recommends using the fuses/circuit breakers listed below to protect service personnel and property in case of component break-down in the frequency converter. ®...
600V depending on the unit's voltage rating. With the Fuses or circuit breakers are mandatory to comply with IEC proper fusing, the frequency converter short circuit current 60364. Danfoss recommends using a selection of the rating (SCCR) is 100,000 Arms. following.
Page 31
600 V depending on the unit's voltage rating. With the Fuses or circuit breakers are mandatory to comply with proper fusing the drive Short Circuit Current Rating (SCCR) NEC 2009. Danfoss recommends using a selection of the is 100,000 Arms. following.
Page 32
5014006-063 KLS-R-60 A6K-60-R 2028220-100 KLS-R-80 A6K-80-R 2028220-125 KLS-R-100 A6K-100-R 2028220-125 KLS-R-125 A6K-125-R 2028220-160 KLS-R-150 A6K-150-R 2028220-200 KLS-R-200 A6K-200-R 2028220-250 KLS-R-250 A6K-250-R Table 3.13 380-500 V, Frame Sizes B and C ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 33
Table 3.16 525-600 V, Frame Sizes B and C Type T indicator fuses of the same size and 170M fuses shown from Bussmann use the -/80 amperage may be substituted. visual indicator. –TN/80 Type T, -/110 or TN/110 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
2 compressors are controlled by the two built-in occurs, the Override Bandwidth overrides the Staging relays. Bandwidth to prevent immediate response to a short duration load change. An Override Bandwidth Timer can ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 35
• If a no load need occurs then destaging ensures that all fixed speed compressors are stopped individually followed by the variable speed compressor. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 36
® How to Install Operating Instructions VLT CDS302 and CDS303 Illustration 3.32 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Now change parameters to testing purposes). Press [Auto On] for running in 1-00 Configuration Mode: Select [3] Process operation and with an external reference. 3-01 Reference/Feedback Unit: Select [71] Bar ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 38
Feedback [unit]. The pressure [bar] is going to be shown in the upper right corner of the display This is what the screen will look like, after configuring the frequency converter for Closed loop application. Illustration 4.4 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 39
Operating Instructions VLT CDS302 and CDS303 Other Compressor Features: To set up other dedicated compressor features press [Quick Menu] and go to Q4 or follow Illustration 4.5. Illustration 4.5 Flowchart ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Status line: Status messages displaying text. 5.1.3 Display Contrast Adjustment ▼ Press [Status] and [ ] for darker display ▲ Press [Status] and [ ] for brighter display ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
[Quick Menu] allows quick access to different Quick Menus select msb (most significant bit) such as: • Stop command from serial communication Q1 - My Personal Menu • Quick stop Q2 - Quick Set-up • DC brake ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Release the keys after 5 s. 5.2.6 Initialisation to Default Settings The frequency converter is now programmed Initialise the frequency converter to default settings in two according to default settings. ways: ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
15-** Drive Information • 16-** Data Readouts • 25-** Cascade Controller • 28-** Compressor Functions After selecting a parameter group, choose a parameter with the navigation keys. The middle section on the ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 44
® How to Program Operating Instructions VLT CDS302 and CDS303 Illustration 5.6 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
1-40 Back EMF at 1000 RPM 4-18 Current Limit 28-42 DC Braking Time 1-44 d-axis Inductance (Ld) 200% I 4-19 Max Output Frequency 28-43 DC Brake Cut In Speed [RPM] Table 6.1 Compressor Related Parameters ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Option: Function: Select the set-up to control the frequency converter functions. Factory setup Cannot be changed. It contains the Danfoss data set, and can be used as a data source when returning the other set-ups to a known state. Set-up 1...
Page 47
(i.e. while the motor is running). Example: Use Multi set-up to shift from Set-up 1 to Set- up 2 whilst the motor is running. Programme in Set-up 1 first, then ensure that Set-up 1 and ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 48
[1693 ] Warning Word 2 [1603] Status Word [1694] Ext. Status Word [1605] Main Actual Value [%] [2580] Cascade Status [1609] Custom Readout [2581 ] Compressor Status [1610] Power [kW] ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 49
Only possible to set different from 0 is when selecting a linear unit [10] 1/min in 0-30 Unit for User-defined [11] Readout. For Quadratic and [12] Pulse/s [20] ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 50
Password is set to [0] Full access, this parameter will be All to LCP Copies all parameters in all set-ups from ignored. the frequency converter memory to the LCP memory. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 51
No access Prevents unauthorised viewing and editing of Quick Menu parameters. NOTE If 0-61 Access to Main Menu w/o Password is set to [0] Full access, this parameter will be ignored. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
If the compressor selection is changed, then all dependent parameters reset to default and any user settings will be lost. Size [] Select the compressor/refrigerant combination dependent. for the system. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
If a Ref 0 (3-02 Minimum No function Reference) is programmed, the preset ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 54
Additional adjustment of the S-ramp ratios or switching This product is then added to the actual initiators may be necessary. reference (X+X*Y/100) to give the resultant actual reference Same options as 3-15 Reference Resource 1. No function ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 55
Additional adjustment of the S-ramp ratios or switching a longer start or stop time. initiators may be necessary. Additional adjustment of the S-ramp ratios or switching initiators may be necessary. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 56
P 1-25 serial communication port. When jog Motor speed state is disabled then the normal ramping times are valid. P 4-11 RPM low limit Time P 3-81 Qramp Qstop Illustration 6.5 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Analog input 54 produce a status signal on Analog input 54 inv terminal 27 or 29 and on relay output 01 or 02. [10] Analog input X30-11 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 58
It is strongly recommended to enable to avoid motor speeds to be avoided. damage. Option: Function: No alarm is displayed if a missing motor phase occurs. NOTE This parameter cannot be adjusted while the motor is running. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
[24] Catch up [28] Slow down [29] Pulse input [32] 29, 33 Ramp bit 0 [34] Ramp bit 1 [35] Mains failure inverse [36] Day/night control [39] DigiPot Increase [55] ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 60
Comp. 1 Inv. interlock [139] Comp. 2 Inv. interlock [140] Comp. 3 Inv. interlock [141] Table 6.4 Functions dedicated to only one digital input are stated in the associated parameter. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 61
(motor potenti- function is not active in process closed loop. ometer). Activate this function by selecting either Freeze reference or Freeze output. When Speed ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 62
INCREASE signal to the Digital Potenti- digital input range and the additional ometer function described in parameter options [60], [61], [63] and [64]. group 3-9* Digital Potmeter. Counters are used in Smart Logic Control functions. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 63
Auto On mode. is at the torque limit, the signal is Logic Stand-by / no The frequency converter is ready for ‘0’. warning operation. No start or stop command is ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 64
The input will go low whenever the Smart low. Logic Action [36] Set dig. out. A low is [65] Comparator 5 See parameter group 13-1* Comparators. executed. If Comparator 4 is evaluated as TRUE, the ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 65
[15] Out of Speed Range principle: [16] Below Speed, low [17] Above Speed, high [18] Out of Feedb. Range [19] Below Feedback, low [20] Above Feedback, high [21] Thermal Warning ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 66
[0 - 110000 Enter the low frequency limit This parameter cannot be adjusted while the motor is corresponding to the low motor shaft running. speed (i.e. low reference value) in ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 67
[48] Bus ctrl., timeout A logical '0' indicates that the output is [51] MCO controlled low or inactive. [100] Output frequency [101] Reference [102] Feedback [103] Motor current ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 68
0.00 % [0.00 - 100.00 Set the output frequency transferred to the output terminal 29 when the terminal is configured as [45] Bus Controlled in 5-63 Terminal 29 Pulse Output Variable. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Overruled to stop Voltage and 6-13 Terminal 53 High Current. Jogging Overruled to jog speed Max. speed Overruled to max. speed Stop and Overruled to stop with subsequent trip trip ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 70
-1 (bar) [Value] Enter the analog input scaling value that to lim 0-20 4-16 Torque Limit Motor Mode corresponds to the minimum reference feedback value set in 3-02 Minimum Reference. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 71
When no signal on the analog output. 20 mA, the output setting of 6-62 Terminal operation X30/8 Max. Scale is: [52] I VLT x 100 0-20mA 38.4 x 100 = 175 % I Motor Norm ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 72
(100%), calculate the percentage value as follows: mA / desired maximum current x 100 % i . e . 10 mA : x 100 = 200 % ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
7-20 Process CL Feedback 1 Resource Option: Function: For process loop with current input, 54 switch has to be positionned on I (current). No function Analog input 53 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 74
1-00 Configuration Mode is set to [3] Process PID control. Process. 7-33 Process PID Proportional Gain Range: Function: 2.00N/A [0.00 - 10.00 Enter the PID proportional gain. The N/A] proportional gain multiplies the error ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 75
T is accomplished via the [72] formula: [73] [74] m WG T = A2/(log(P+1)-A1) – A3 [170] [171] lb/in2 where A1, A2 and A3 are refrigerant dependent constants. [172] in WG [173] ft WG ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 76
Cut-in level and the compressor must run. to Temperature Conversion). Another situation could be that the start situation is where the feedback is between Cut-out and Cut-in. In that case, no STOP is initiated. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 77
7-82 Cut-in Value Range: Function: 3 bar [Par.7-81 – Select the Cut-in Level where the stop 3000] signal is de-activated and the compressor starts. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
0-12 This Set-up Linked to. communication has stopped. The function selected in 8-04 Control Word Timeout Function is then carried out. A ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 79
Depended on the profile set in delays. 8-10 Control Profile. Alarm 68 Only The input goes high whenever Alarm 68 is active and goes low whenever no alarm 68 is actived Trip excl Alarm 68 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 80
OR via one 8-52 DC Brake Select of the digital inputs. Option: Function: Select control of the DC brake via the terminals (digital input) and/or via the fieldbus. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 81
(e.g. CRC fault), detected on the bus. 8-82 Slave Messages Rcvd Range: Function: [0 - 0 ] This parameter shows the number of valid telegrams addressed to the slave, sent by the frequency converter. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
[0] / action [0]. The ranges set in 4-50 Warning Current illustration shows an example with three event / actions: Low to 4-53 Warning Speed High. On reference The motor is running on reference. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 83
In range [26] Logic rule 0 Use the result of logic rule 0. On reference Torque limit [27] Logic rule 1 Use the result of logic rule 1. Current limit ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 85
Motor speed [RPM] or [Hz] ranges set in 4-50 Warning Current Low to 4-53 Warning Speed High. Motor current [60] On reference The motor is running on reference. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 86
High when 3-13 Reference Site = [2] [92] Brake fault (IGBT) The brake IGBT is short circuited. Local or when 3-13 Reference Site is [0] [93] Mech. brake The mechanical brake is active. control ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 89
[39] Start command Timer 0, select index 1 to program Timer 1, and so on. [40] Drive stopped [41] Reset Trip [42] Auto-reset Trip [43] Ok key [44] Reset key ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 90
[71] SL Time-out 4 On reference [72] SL Time-out 5 Torque limit [73] SL Time-out 6 Current limit [74] SL Time-out 7 Out of current range [75] Start command given ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 91
Boolean 1 and 13-42 Logic Rule Boolean 2. [17] Mains out of range [13-**] signifies the boolean input of [18] Reversing parameter group 13-** Smart Logic Control. [19] Warning [20] Alarm (trip) [21] Alarm (trip lock) ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 92
Digital input x46/11 [85] Digital input x46/13 [90] ATEX ETR cur. warning Selectable if 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If the alarm ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 93
[17] Mains out of range [85] Digital input x46/13 [18] Reversing [90] ATEX ETR cur. warning Selectable if 1-90 Motor Thermal [19] Warning Protection is set to [20] ATEX ETR ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 94
Digital input x30/2 Below I low [77] Digital input x30/3 Above I high [78] Digital input x30/4 [10] Out of speed range [79] Digital input x46/1 [11] Below speed low ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 95
Changes the active set-up (0-10 Active Set- [15] Select preset ref Selects preset reference 5. up) to ‘1’. If the active preset reference is changed, it will merge with other preset reference ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 96
Any output with SL output B will be low. [34] Set digital out C Any output with SL output Cwill be low. [35] Set digital out Any output with SL output D will be low. D low ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
10 automatic resets after tripping. Set switches S201 (A53) and S202 (A54) = ON./I. Insert the test plug (see below). Connect to mains supply. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 98
[0] Normal operation. converter) when running with reduced pump speed after load on the frequency converter has exceeded the allowable limit (110% for 60 s). ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 99
Table 6.11 Table for Selection of Choice of Action when Selected Alarm Appears D = Default setting. x = possible selection. 1) Only high power drives In FC small and medium A69 is only a warning ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
15-06 Reset kWh Counter Option: Function: Do not reset Nno reset of the kWh counter is desired. Reset counter Press [OK] to reset the kWh counter to zero (see 15-02 kWh Counter). ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Consequently, the min. value and the max. actual motor voltage and motor current. value will depend on the max. motor current The value is filtered, and therefore approx. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 102
Consequently, the min. value nameplate data on the connected and the max. value will depend on the max. motor current as well as the ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 103
16-52 Feedback [Unit] Range: Function: 0.000 Reference- [-999999.999 - View the feedback unit FeedbackUnit 999999.999 resulting from the ReferenceFeed- selection of unit and backUnit] scaling in 3-00 Reference Range, 3-01 Reference/ ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 104
[3] Pt 1000 [°F] [4] Ni 1000 [°C] [5] Ni 1000 [°F] 16-62 Analog Input 53 Range: Function: 0.000 [-20.000 - 20.000 ] View the actual value at input 53. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 105
Control word depends on the Fieldbus [0 - 4294967295 ] View the warning word sent via the option installed and the Control word profile serial communication port in hex code. selected in 8-10 Control Profile. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 106
16-95 Ext. Status Word 2 Range: Function: [0 - 4294967295 ] Returns the extended warning word 2 sent via the serial communication port in hex code. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Illustration 6.25 Cascade Controller Feedback Signals ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 108
® Parameter Descriptions Operating Instructions VLT CDS302 and CDS303 Illustration 6.26 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 109
Parameters for setting the bandwidth within which the disconnected to have equal running hours for pressure/temperature will be allowed to operate before each compressor. staging/destaging fixed speed compressors. Also includes various timers to stabilize the control. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 110
Cascade Controller must stop the system immediately by cutting out all the fixed speed compressors. This is basically the same as Emergency Stop (Coast/Coast inverse Command) for the Cascade Controller. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 111
25-29 Destage Function Option: Function: Disabled Enabled The Destage Function ensures that the lowest numbers of compressors are running to save energy. If the Destage Function is set to [0] ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 112
“Destaging Speed” the fixed speed until a preset time after the stopping of the compressor is destaged. The Destaging Threshold ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 113
“Staging Speed” the fixed speed compressor is staged on. Staging Speed calculation is based on 25-42 Staging Threshold and 4-14 Motor Speed High Illustration 6.36 Limit [Hz]. Staging Speed is calculated with the following formula: ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 114
(bottom graph) are running before the Range: Function: staging command. When the [0] Slow transfer command is 24 h [1 – 999 If [1] Alternation Time Interval option in 25-51 Alternation Event is selected, the ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 115
Mode at Alternation and Illustration 6.37 Destaging The Pack Controller is destaging fixed speed for description of staging and compressors. alternation. Lead Not Set No compressor available to be assigned as variable speed compressor. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 116
The default value of each Compressor ON Time counter value of Manual Alternation is [0] Off. If a can be reset to 0 by writing in the ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 117
[0] Off. If the parameter is set to the number which equals the actual variable speed compressor, the parameter will be reset to [0] immediately after. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
[10 – 120 s ] This parameter controls the duration of oil itself in pipes and bends. The oil deposits can be returned return boosts. to the crankcase by increasing velocity for short periods at ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 119
10 Hz lower than the [160] ˚F previous step. The initial step occurs when the discharge temperature rises from below to above warning level and ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 120
[0 – 60.0 Sec] Set the duration of the DC-brake Activate the DC-hold current when the motor is current. stopped. The current level is defined in 28-31 Heating DC Current. Disabled ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 121
Motor Speed Low Limit is 1800 RPM the four calculated intervals become Low: 1800 RPM ≤ speed < 2350 RPM Med: 2350 RPM ≤ speed < 3450 RPM High: 3450 RPM ≤ speed < 4550 RPM ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
0.1. The value 100 is therefore read as 10.0. Examples: 0s ⇒ conversion index 0 0.00s ⇒ conversion index -2 0ms ⇒ conversion index -3 0.00ms ⇒ conversion index -5 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 123
Set Date and Time ExpressionLimit All set-ups TRUE 0-71 Date Format ExpressionLimit 1 set-up TRUE Uint8 0-72 Time Format ExpressionLimit 1 set-up TRUE Uint8 0-74 DST/Summertime [0] Off 1 set-up TRUE Uint8 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 124
0-82 Additional Working Days ExpressionLimit 1 set-up TRUE TimeOf 0-83 Additional Non-Working Days ExpressionLimit 1 set-up TRUE VisStr[2 0-89 Date and Time Readout 0 N/A All set-ups TRUE Table 6.18 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 125
All set-ups TRUE Uint8 1-73 Flying Start ExpressionLimit All set-ups FALSE Uint8 1-74 Start Speed [RPM] ExpressionLimit All set-ups TRUE Uint16 1-75 Start Speed [Hz] ExpressionLimit All set-ups TRUE Uint16 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 126
1-90 Motor Thermal Protection ExpressionLimit All set-ups TRUE Uint8 1-91 Motor External Fan [0] None All set-ups TRUE Uint8 1-93 Thermistor Source [0] None All set-ups TRUE Uint8 Table 6.19 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 127
All set-ups TRUE Uint8 3-93 Maximum Limit 100 % All set-ups TRUE Int16 3-94 Minimum Limit All set-ups TRUE Int16 3-95 Ramp Delay 1 N/A All set-ups TRUE TimD Table 6.20 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 128
Bypass Speed To [RPM] ExpressionLimit All set-ups TRUE Uint16 4-63 Bypass Speed To [Hz] ExpressionLimit All set-ups TRUE Uint16 4-64 Semi-Auto Bypass Set-up [0] Off All set-ups FALSE Uint8 Table 6.21 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 129
TRUE Uint16 5-95 Pulse Out #29 Bus Control All set-ups TRUE 5-96 Pulse Out #29 Timeout Preset 1 set-up TRUE Uint16 5-97 Pulse Out #X30/6 Bus Control All set-ups TRUE ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 130
CDS302 and CDS303 Par. Parameter description Default value 4-set-up Change Conver- Type No. # during sion index operation 5-98 Pulse Out #X30/6 Timeout Preset 1 set-up TRUE Uint16 Table 6.22 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 131
Uint8 6-61 Terminal X30/8 Min. Scale All set-ups TRUE Int16 6-62 Terminal X30/8 Max. Scale 100 % All set-ups TRUE Int16 6-63 Terminal X30/8 Output Bus Control All set-ups TRUE ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 132
CDS302 and CDS303 Par. Parameter description Default value 4-set-up Change Conver- Type No. # during sion index operation 6-64 Terminal X30/8 Output Timeout Preset 1 set-up TRUE Uint16 Table 6.23 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 133
Process PID Diff. Gain Limit 5.0 N/A All set-ups TRUE Uint16 7-38 Process PID Feed Forward Factor All set-ups TRUE Uint16 7-39 On Reference Bandwidth All set-ups TRUE Uint8 Table 6.24 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 134
Uint16 8-94 Bus Feedback 1 0 N/A 1 set-up TRUE 8-95 Bus Feedback 2 0 N/A 1 set-up TRUE 8-96 Bus Feedback 3 0 N/A 1 set-up TRUE Table 6.25 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 135
[0] Trip All set-ups TRUE Uint8 14-61 Function at Inverter Overload [0] Trip All set-ups TRUE Uint8 14-62 Inv. Overload Derate Current 95 % All set-ups TRUE Uint16 Table 6.26 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 136
15-63 Option Serial No 0 N/A All set-ups FALSE VisStr[18] 15-70 Option in Slot A 0 N/A All set-ups FALSE VisStr[30] 15-71 Slot A Option SW Version 0 N/A All set-ups FALSE VisStr[20] ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 137
15-9* Parameter Info 15-92 Defined Parameters 0 N/A All set-ups FALSE Uint16 15-93 Modified Parameters 0 N/A All set-ups FALSE Uint16 15-99 Parameter Metadata 0 N/A All set-ups FALSE Uint16 Table 6.27 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 138
Pulse Input #29 [Hz] 0 N/A All set-ups FALSE Int32 16-68 Pulse Input #33 [Hz] 0 N/A All set-ups FALSE Int32 16-69 Pulse Output #27 [Hz] 0 N/A All set-ups FALSE Int32 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 139
Ext. Status Word 0 N/A All set-ups FALSE Uint32 16-95 Ext. Status Word 2 0 N/A All set-ups FALSE Uint32 16-96 Maintenance Word 0 N/A All set-ups FALSE Uint32 Table 6.28 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 140
25-88 Pack capacity [%] All set-ups TRUE Uint16 25-9* Service 25-90 Compressor Interlock [0] Off All set-ups TRUE Uint8 25-91 Manual Alternation 0 N/A All set-ups TRUE Uint8 Table 6.29 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 141
0 N/A All set-ups TRUE Int16 28-9* Injection Control 28-90 Injection On [0] Off All set-ups TRUE Uint8 28-91 Delayed Compressor Start [0] No All set-ups TRUE Uint8 Table 6.30 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
DC link voltage low DC over-voltage DC under voltage Inverter overloaded Motor ETR over temperature 1-90 Motor Thermal Protection Motor thermistor over temperature 1-90 Motor Thermal Protection Torque limit Over Current ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 143
1.8 V supply low Speed limit 1-86 Trip Speed Low [RPM] AMA calibration failed AMA check U and I AMA low I AMA motor too big AMA motor too small ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 144
[Reset] 1) Can not be Auto reset via 14-20 Reset Mode or make a reset by a digital input (parameter group 5-1* ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 145
Mains ph. Loss (W4) Out of Speed Range 00008000 32768 AMA Not OK reserved No Motor (W3) OVC Active 00010000 65536 Live Zero Error (A2) reserved Live Zero Error (W2) AC Brake ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 146
This warning or alarm only appears if programmed by the frequency converter. user in 6-01 Live Zero Timeout Function. The signal on one of the analog inputs is less than 50% of the minimum ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 147
18 or 19 (digital input PNP only) The fault is that the frequency converter has run with and terminal 50. Check 1-93 Thermistor Source more than 100% overload for too long. selects terminal 18 or 19. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 148
The fan warning function is an extra protective function that checks if the fan is running/mounted. The fan warning 15-42 Voltage can be disabled in 14-53 Fan Monitor ([0] Disabled). ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 149
The temperature fault will not reset until the temperature falls below a defined heatsink temperature. Check for loose or missing wiring The trip and reset points are different based on the frequency converter power size. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 150
Troubleshooting Operating Instructions VLT CDS302 and CDS303 It may be necessary to contact your Danfoss supplier or WARNING 42, Overload of digital output on X30/6 or service department. Note the code number for further overload of digital output on X30/7 troubleshooting directions.
Page 151
Operating Instructions VLT CDS302 and CDS303 ALARM 50, AMA calibration failed WARNING/ALARM 65, Control card over temperature The cutout temperature of the control card is 80 °C. Contact your Danfoss supplier or Danfoss Service Department. Troubleshooting • ALARM 51, AMA check U...
Page 152
ALARM 81, CSIV corrupt and the typecode changed. Reset to remove the warning CSIV file has syntax errors. and resume normal operation. ALARM 82, CSIV parameter error CSIV failed to init a parameter. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Further options and customer load may add up to 30W to the losses. (Though typical only 4 W extra for a fully loaded control card, or options for slot A or slot B, each). ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 154
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (±5%). 5) The three values for the max. cable cross section are for single core, flexible wire and flexible wire with sleeve, respectively. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 155
1) High overload = 160% torque during 60 s., Normal overload = 110% torque during 60 s. 2) American Wire Gauge. 3) Measured using 5 m screened motor cables at rated load and rated frequency. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 156
Max. cable cross-section with Disconnect (AWG)] Estimated power loss at rated max. load [W] Weight, enclosure IP21, [kg] Weight, 23.5 23.5 enclosure IP20 [kg] 0.98 0.98 0.98 Efficiency Table 8.3 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 157
EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe use of the Safe Stop function follow the related information and instructions in the Application Guidelines. ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 158
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals Control Card, RS-485 Serial Communication Terminal number 68 (P,TX+, RX+), 69 (N,TX-, RX-) Terminal number 61 Common for terminals 68 and 69 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...
Page 159
Derating for high altitude, see section on special conditions EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3 EN 61800-3, EN 61000-6-1/2, EMC standards, Immunity EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6 ® MG34M302 - VLT is a registered Danfoss trademark/Commercial Compressor...