Parameter Description
1-20 Motor Power [kW]
Range:
Function:
Size
[
0.09 -
Enter the nominal motor power in kW
related
3000.00
according to the motor nameplate data.
*
kW]
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running. Depending
on the choices made in 0-03 Regional
Settings, either 1-20 Motor Power [kW] or
1-21 Motor Power [HP] is made invisible.
1-21 Motor Power [HP]
Range:
Function:
Size
[
0.09 -
Enter the nominal motor power in HP
related
3000.00 hp]
according to the motor nameplate data.
*
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running.
Depending on the choices made in
0-03 Regional Settings, either 1-20 Motor
Power [kW] or 1-21 Motor Power [HP] is
made invisible.
1-22 Motor Voltage
Range:
Function:
Size
[
10. -
Enter the nominal motor voltage
related
1000. V]
according to the motor nameplate
*
data. The default value corresponds to
the nominal rated output of the unit.
This parameter cannot be adjusted
while the motor is running.
1-23 Motor Frequency
Range:
Function:
Size
[20 -
Select the motor frequency value from
related
1000 Hz]
the motor nameplate data.For 87 Hz
*
operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt
4-13 Motor Speed High Limit [RPM] and
3-03 Maximum Reference to the 87 Hz
application.
NOTE
This parameter cannot be adjusted while the motor is
running.
®
VLT
HVAC Drive Programming Guide
1-24 Motor Current
Range:
Size
related
NOTE
This parameter cannot be adjusted while the motor is
running.
1-25 Motor Nominal Speed
Range:
Size related
NOTE
This parameter cannot be adjusted while the motor is
running.
1-26 Motor Cont. Rated Torque
Range:
Size
related
1-28 Motor Rotation Check
Option:
[0]
[1]
Pressing [OK], [Back] or [Cancel] will dismiss the message
and display a new message: "Press [Hand on] to start the
motor. Press [Cancel] to abort". Pressing [Hand on] starts
the motor at 5 Hz in forward direction and the display
shows: "Motor is running. Check if motor rotation direction
®
MG.11.CC.02 - VLT
is a registered Danfoss trademark
Function:
[
0.10 -
Enter the nominal motor current
10000.00 A]
value from the motor nameplate
*
data. This data is used for
calculating motor torque, motor
thermal protection etc.
Function:
[100 - 60000
Enter the nominal motor speed
*
RPM]
value from the motor nameplate
data. This data is used for
calculating automatic motor
compensations.
Function:
[0.1 -
Enter the value from the motor
10000.0 Nm]
nameplate data. The default value
*
corresponds to the nominal rated
output. This parameter is available
when 1-10 Motor Construction is set to
PM, non salient SPM [1], i.e. the
parameter is valid for PM and
nonsalient SPM motors only.
Function:
Following installation and connection of the
motor, this function allows the correct motor
rotation direction to be verified. Enabling this
function overrides any bus commands or digital
inputs, except External Interlock and Safe Stop (if
included).
Off
Motor Rotation Check is not active.
*
Enabled Motor Rotation Check is enabled. Once enabled,
Display shows:
"Note! Motor may run in wrong direction".
3
3
39