Parameter Description
8-56 Preset Reference Select
Option:
[0]
Digital
input
[1]
Bus
3
3
[2]
Logic AND Activates Preset Reference selection via the
[3]
Logic OR
*
3.9.6 8-7* BACnet
8-70 BACnet Device Instance
Range:
1
[0 - 4194302 ] Enter a unique ID number for the BACnet
*
8-72 MS/TP Max Masters
Range:
127
[1 - 127 ] Define the address of the master which holds
*
NOTE
This parameter is active only when 8-30 Protocol is set to
[9] FC Option.
8-73 MS/TP Max Info Frames
Range:
1
[1 - 65534 ] Define how many info/data frames the device
*
NOTE
This parameter is active only when 8-30 Protocol is set to
[9] FC Option.
8-74 "I-Am" Service
Option:
[0]
Send at power-
*
up
[1]
Continuously
NOTE
This parameter is active only when 8-30 Protocol is set to
[9] FC Option.
86
VLT
Function:
Activates Preset Reference selection via a
digital input.
Activates Preset Reference selection via the
serial communication port or fieldbus option.
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
Activates the Preset Reference selection via the
fieldbus/serial communication port OR via one
of the digital inputs.
Function:
device.
Function:
the highest address in this network.
Decreasing this value optimises polling for the
token.
Function:
is allowed to send while holding the token.
Function:
Choose whether the device should send
the "I-Am" service message only at
power-up or continuously with an
interval of approx. 1 min.
MG.11.CC.02 - VLT
®
HVAC Drive Programming Guide
8-75 Initialisation Password
Range:
Size related
*
NOTE
This parameter is active only when 8-30 Protocol is set to
[9] FC Option.
3.9.7 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus
communication via the FC Port.
8-80 Bus Message Count
Range:
0
[0 - 0 ] This parameter shows the number of valid
*
8-81 Bus Error Count
Range:
0
[0 - 0 ] This parameter shows the number of telegrams
*
8-82 Slave Messages Rcvd
Range:
0
[0 - 0 ] This parameter shows the number of valid
*
8-83 Slave Error Count
Range:
0
[0 - 0 ] This parameter shows the number of error
*
8-84 Slave Messages Sent
Range:
0
[0 - 0 ] This parameter shows the number of messages
*
8-85 Slave Timeout Errors
Range:
0
[0 - 0 ] This parameter shows the number of messages
*
3.9.8 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range:
100 RPM
*
RPM]
®
is a registered Danfoss trademark
Function:
[1 - 1 ] Enter the password needed for execution
of Drive Re-initialisation from BACnet.
Function:
telegrams detected on the bus.
Function:
with faults (e.g. CRC fault), detected on the bus.
Function:
telegrams addressed to the slave, sent by the
frequency converter.
Function:
telegrams, which could not be executed by the
frequency converter.
Function:
sent from this drive
Function:
suppressed due to time-out.
Function:
[
0 - par. 4-13
Enter the jog speed. This is a fixed
jog speed activated via the serial
port or fieldbus option.