Parameter Description
3.16.6 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Range:
0
[0 - 4294967295 ] View the alarm word sent via the serial
*
3
3
16-91 Alarm Word 2
Range:
0
[0 - 4294967295 ] View the alarm word 2 sent via the
*
16-92 Warning Word
Range:
0
[0 - 4294967295 ] View the warning word sent via the
*
16-93 Warning Word 2
Range:
0
[0 - 4294967295 ] View the warning word 2 sent via the
*
16-94 Ext. Status Word
Range:
0
[0 - 4294967295 ] Returns the extended status word sent
*
16-95 Ext. Status Word 2
Range:
0
[0 - 4294967295 ] Returns the extended warning word 2
*
16-96 Maintenance Word
Range:
0
[0 -
4294967295 ]
*
124
®
VLT
Function:
communication port in hex code.
Function:
serial communication port in hex code.
Function:
serial communication port in hex code.
Function:
serial communication port in hex code.
Function:
via the serial communication port in hex
code.
Function:
sent via the serial communication port
in hex code.
Function:
Readout of the Preventive Maintenance
Word. The bits reflect the status for the
programmed Preventive Maintenance Events
in parameter group 23-1*. 13 bits represent
combinations of all the possible items:
Bit 0: Motor bearings
Bit 1: Pump bearings
Bit 2: Fan bearings
Bit 3: Valve
Bit 4: Pressure transmitter
Bit 5: Flow transmitter
Bit 6: Temperature transmitter
Bit 7: Pump seals
Bit 8: Fan belt
Bit 9: Filter
MG.11.CC.02 - VLT
HVAC Drive Programming Guide
16-96 Maintenance Word
Range:
®
is a registered Danfoss trademark
Function:
Bit 10: Drive cooling fan
Bit 11: Drive system health check
Bit 12: Warranty
Bit 13: Maintenance Text 0
Bit 14: Maintenance Text 1
Bit 15: Maintenance Text 2
Bit 16: Maintenance Text 3
Bit 17: Maintenance Text 4
Positio
Valve
Fan
Pump
bearing
bearing
n 4⇒
s
s
Positio
Pump
Temper
Flow
n 3 ⇒
seals
ature
transmi
transmi
tter
tter
Positio
Drive
Drive
Filter
n 2 ⇒
system
cooling
health
fan
check
Positio
n 1⇒
0
-
-
-
hex
1
-
-
-
hex
2
-
-
+
hex
3
-
-
+
hex
4
-
+
-
hex
5
-
+
-
hex
6
-
+
+
hex
7
-
+
+
hex
8
+
-
-
hex
9
+
-
-
hex
A
+
-
+
hex
B
+
-
+
hex
C
+
+
-
hex
D
+
+
-
hex
E
+
+
+
hex
F
+
+
+
hex
Example:
The Preventive Maintenance Word shows
040Ahex.
Position
1
2
3
hex-value
0
4
0
The first digit 0 indicates that no items from
the fourth row requires maintenance
The second digit 4 refers to the third row
indicating that the Drive Cooling Fan requires
maintenance
Motor
bearing
s
Pressur
e
transmi
tter
Fan
belt
Warrant
y
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
4
A

Advertisement