Danfoss VLT Series Programming Manual page 103

Hvac drive
Hide thumbs Also See for VLT Series:
Table of Contents

Advertisement

Parameter Description
3.13.4 13-2* Timers
Use the result (TRUE or FALSE) from timers directly to
define an event (see 13-51 SL Controller Event), or as
boolean input in a logic rule (see 13-40 Logic Rule Boolean
3
3
1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule Boolean 3).
A timer is only FALSE when started by an action (i.e. Start
timer 1 [29]) until the timer value entered in this
parameter is elapsed. Then it becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Array [3]
Range:
Size
related
0.000 ]
*
3.13.5 13-4* Logic Rules
Combine up to three boolean inputs (TRUE / FALSE inputs)
from timers, comparators, digital inputs, status bits and
events using the logical operators AND, OR, and NOT.
Select boolean inputs for the calculation in 13-40 Logic Rule
Boolean 1, 13-42 Logic Rule Boolean 2 and 13-44 Logic Rule
Boolean 3. Define the operators used to logically combine
the selected inputs in 13-41 Logic Rule Operator 1 and
13-43 Logic Rule Operator 2.
Par. LC-40
Logic Rule Boolean 1
Par. LC-42
Logic Rule Boolean 2
Priority of calculation
The results of 13-40 Logic Rule Boolean 1, 13-41 Logic Rule
Operator 1 and 13-42 Logic Rule Boolean 2 are calculated
first. The outcome (TRUE / FALSE) of this calculation is
combined with the settings of 13-43 Logic Rule Operator 2
and 13-44 Logic Rule Boolean 3, yielding the final result
(TRUE / FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option:
[0]
False
*
102
Function:
[
0.000 -
Enter the value to define the duration
of the FALSE output from the
programmed timer. A timer is only
FALSE if it is started by an action (i.e.
Start timer 1 [29]) and until the given
timer value has elapsed.
Par. LC-41
Par. LC-43
Logic Rule Operator 1
Logic Rule Operator 2
. . .
. . .
. . .
. . .
Par. LC-44
Logic Rule Boolean 3
Function:
Enters the fixed value of FALSE in the
logic rule.
MG.11.CC.02 - VLT
®
VLT
HVAC Drive Programming Guide
13-40 Logic Rule Boolean 1
Array [6]
Option:
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range See parameter group 5-3* for further
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
®
is a registered Danfoss trademark
Function:
Enters the fixed value TRUE in the
logic rule.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
See parameter group 5-3* for further
description.
Use the result of comparator 0 in the
logic rule.
Use the result of comparator 1 in the
logic rule.