Parameter Description
8-05 End-of-Timeout Function
Option:
3
3
[1]
Resume set-
*
up
8-06 Reset Control Timeout
Option:
[0]
Do not
*
reset
[1]
Do reset Returns the frequency converter to the original
8-07 Diagnosis Trigger
Option:
[0]
Disable
*
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Profile
Option:
[0]
FC profile
*
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
Option:
[0]
No function
[1]
Profile Default
*
[2]
Alarm 68 Only
82
VLT
Function:
until 8-06 Reset Control Timeout toggles. Then
the frequency converter resumes its original
set-up.
Resumes the set-up active prior to the time-
out.
Function:
This parameter is active only when the choice
Hold set-up [0] has been selected in 8-05 End-of-
Timeout Function .
Retains the set-up specified in 8-04 Control
Timeout Function, [Select setup 1-4] following a
control time-out.
set-up following a control word time-out. When
the value is set to Do reset [1], the frequency
converter performs the reset and then
immediately reverts to the Do not reset [0]
setting.
Function:
This parameter has no function for
BACnet.
Function:
Select the interpretation of the control
and status words corresponding to the
installed fieldbus. Only the selections
valid for the fieldbus installed in slot A
will be visible in the LCP display.
Function:
This parameter enables configuration of
bits 12 – 15 in the status word.
Function corresponds to the profile
default selected in 8-10 Control Profile.
Only set in case of an Alarm 68.
MG.11.CC.02 - VLT
®
HVAC Drive Programming Guide
8-13 Configurable Status Word STW
Option:
[3]
Trip excl Alarm
68
[10] T18 DI status.
[11] T19 DI status.
[12] T27 DI status.
[13] T29 DI status.
[14] T32 DI status.
[15] T33 DI status.
[16] T37 DI status
[21] Thermal
warning
[30] Brake fault
(IGBT)
[40] Out of ref
range
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic Rule 0
[71] Logic Rule 1
®
is a registered Danfoss trademark
Function:
Set in case of a trip, except if the trip is
executed by an Alarm 68.
The bit indicates the status of terminal
*1
18
.
The bit indicates the status of terminal
19
*1
.
The bit indicates the status of terminal
*1
27
.
The bit indicates the status of terminal
*1
29
.
The bit indicates the status of terminal
32
*1
.
The bit indicates the status of terminal
*1
33
.
The bit indicates the status of terminal
37
*2
.
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
Output is Logic '1' when the brake IGBT is
short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
See parameter group 13-1*. If Comparator
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group 13-1*. If Comparator
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group 13-1*. If Comparator
2 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group 13-1*. If Comparator
3 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group 13-1*. If Comparator
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group 13-1*. If Comparator
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group 13-4*. If Logic Rule
0 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group 13-4*. If Logic Rule
1 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.