1 3 . 6 C h a n g e I n p u t s
By default, all inputs are pre-set as 'unused' so you will need to program each individual input you require.
The input will not be 'live' (and hence cannot be walk tested) until you have exited the Engineer Menu
(please see Page: 13)
Before programming, identify the location of each input from the following tables on page Error! Bookmark
not defined..

13.6.1 Input Types

Number & Type
00
Unused
01
Fire
02
Gas
03
HU
04
Silent HU
05
Tamper
06
Immediate
07
Entry/Exit (EE)
08
Access (A)
09
A (Part EE)
10
EE (Part A)
11
PTS
12
Switcher
13
24 Hour
RINS871-3
Operation
Factory default
Input is programmed out of operation.
Active at all times
Audible response: Full (differentiated).
Communicator: 'Fire' signal
Active at all times
Audible response: Full (differentiated)
Communicator: 'Gas' signal
Active at all times
Audible Response: Full (differentiated)
Communicator: 'Hold Up' and 'Input HU' signals
Active at all times
Audible Response: None
Communicator: 'Hold Up' and 'Input HU' signals
When disarmed:
Audible Response: Internal only
Communicator: 'Tamper' signal
When armed:
Audible Response: Full (differentiated)
Communicator: 'Tamper' and 'Intruder' signals
Active when armed
Audible Response: Full
Communicator: 'Intruder' signal
Active when armed – initiates entry timer if system not disarmed before entry
time expires:
Audible Response: Full
Communicator: 'Intruder' signal
Active when armed, except during entry time
Audible Response: Full
Communicator: 'Intruder' signal
When fully armed, acts as Access input, as above
When part armed, acts as Entry/Exit input, as above
When fully armed, acts as Entry/Exit input, as above
When part armed, acts as Access input, as above
Active during exit time to complete arming procedure
No audible or communicator response.
Note: May be used to act as 'doorbell' by use of 'chime' attribute.
Active at all times
No audible or communicator response
Triggers associated output or switches other equipment
When armed:
Audible Response: Full
P C X S M S A N D P C X 2 5 6 S Y S T E M M A N U A L