Appendix A: Faults; Device Fail; Fault Indications - Pyronix 256 System Manual

Table of Contents

Advertisement

If a device on the PCX system is not installed correctly or has lost its communication with the
panel, "DEVICE FAIL" will be shown on the LCD keypad followed by a 3-figure device code. The
first digit identifies each type of device:
D E V I C E F A I L 1 0 0 = E n d S t a t i o n
D E V I C E F A I L 2 0 0 = K e y p a d
D E V I C E F A I L 3 0 0 = T a g R e a d e r / D o o r S t a t i o n / R I X 2
D E V I C E F A I L 4 0 0 = R e m o t e I n p u t E x p a n d e r
D E V I C E F A I L 5 0 0 = R e m o t e O u t p u t E x p a n d e r
The digits after refer to that devices address, for example:
DEVICE FAIL 401 = means that the Remote Input Expander addressed as "01" has a problem.
Fault
Description
End Station unable to
MODEM
FAULT
communicate with Digi Modem
DIGI FAIL
Call to ARC from Digi Modem
COMM
DigiModem has failed.
Note: This is a
communication problem,
which is rarely caused by
an equipment fault.
PHC TEST
Unable to communicate with
Pyronix Host Computer.
FAIL
Note: This would also
result if the telephone line
had premium rate calls
blocked.
LINE FAULT
PSTN Line Fault signalled by
100
Digi Modem.
ATE LINE
PSTN Line Fault signalled by
FAULT
device using STU/ATE pins on
End Station.
ATE FAIL
Call to ARC from device
COMM
using End Station STU/ATE
pins has failed. Note: This
is a communication
problem, which is rarely
caused by equipment
RINS871-3
P C X S M S A N D P C X 2 5 6 S Y S T E M M A N U A L
A P P E N D I X A :
D e v i c e F a i l
F a u l t I n d i c a t i o n s
COMMUNICATION FAULTS
Solution
If modem not present, ensure that "Disable Digi" option
is set to 'YES' and "DOWNLOAD MODE" is set to
'NONE' or 'RS232'.
If present, but not detected, check Digi Modem is
inserted correctly and complete initialisation by pressing
End Station 'RESET' button for 2 seconds.
Check ALL call details are programmed correctly.
Ensure signalling format is correctly set for ARC
receiver.
If only one call number programmed, ensure "STOP ON
SUCCESS" = 'YES' and "TRY SAME" is selected – NOT
"TRY NEXT".
Ensure Digi is enabled, and at least one SMS call is
correctly programmed.
Check that ordinary phone on same line connects to
PHC and modem tones heard - if not, problem is PSTN
– NOT equipment.
De-program SMS content types for each call, exit
Engineer menu, press RESTART button, and retry PHC
test from Manager menu.
Only operative if "DOWNLOAD BY MODEM" selected
OR "DISABLE DIGI/SMS" is set to 'NO'
Note: 'Line Fault' timer operative.
Only operative if Site Option "DIGIREPLY" is set to
'STU' or 'Digicom.' Check voltage on input pin – if +5/12
volts, device connected is showing fault.
Note: 'Line Fault' timer operative
Only operative if Site Option "DIGIREPLY" is set to
'Digicom.'
Check voltage on input pin - if +5/12 volts, device
connected is showing fault.
F A U L T S
Page: 143