1 3 . 3 S o f t w a r e R e v i s i o n
This option identifies the software version number, software serial number and product, and should always
be checked before contacting Customer Support.
V i s u a l K e y p a d P r o g r a m m i n g P r o c e d u r e
Using the
and

REVISION?'

Press the
key
The following will be displayed (on a PCX 256)
Press the
key
You will be returned to the Engineer Menu.
1 3 . 4 C h o o s e M o d e
This option allows you to select the following options:

13.4.1 The End of Line Range

Please note this feature is not on the PCX 26/SMS
This programs the panel to operate with different resistor values:
1K1 = Alarm: 1K1, Tamper: 1K1.
2K2 = Alarm: 4K7, Tamper: 2K2.
4K7 = Alarm: 4K7, Tamper: 4K7.

13.4.2 SEOL or DEOL

This programs whether the alarm panel and any Remote Input Expanders will be used in Singe End of Line
(SEOL) or Double End of Line (DEOL) resistor mode. This is a global selection, including keypads, etc.

13.4.3 Input Response Time

This selects the time that a input trigger must be present before the system responds by generating an
alarm, and is programmable from 100ms (0.1 seconds) to 3000ms (3 seconds). This is a global selection.
Note: Settings below 400ms or above 800ms do not comply with EN50131 (or BS4737), and are provided
purely for diagnostic purposes. Higher settings are more resistant to false stimuli.

13.4.4 Input XDF

DO NOT CHANGE THIS SETTING UNLESS INSTRUCTED TO BY CUSTOMER SUPPORT.