Primus XCONTROL PLUS Original Programming Manual page 94

Industrial washer extractors
Table of Contents

Advertisement

Err N°
Failure
Failure Name
326
Err CTE
PU short circuit
327
Err P24
24VDC short circuit
328
Err MB1*
Brake sequence
error 1
329
Err MB2*
Brake sequence
error 2
330
Err MB3*
Brake sequence
error 3
331
Err MB4*
Brake sequence
error 4
332
Err MB5*
Brake sequence
error 5
333
Err MB6*
Brake sequence
error 6
334
Err MB7*
Brake sequence
error 7
335
Err FIN
Heatsink overheat
336
Err OSD*
Speed deviation
excess
337
Err ECT*
Encoder signal loss
338
Err E.1*
Option
alarm(connector1)
339
Err E.2*
Option
alarm(connector2)
340
Err E.3*
Option
alarm(connector3)
341
Err ILF*
Input phase failure
342
Err PTC
PTC thermistor
operation
343
Err PE2
Parameter storage
error
344
Err CDO*
Output Current
detection
345
Err IOH
Inrush overheat
346
Err SER*
Communication
error
347
Err AIE*
Analog input error
348
Err USB*
USB communication
error
349
Err OS*
Overspeed
350
Err OD*
Position error
94
Explanation
Short circuit on the RS485 communication connector.
Check for short circuit in the communication cable.
Short circuit on the 24VDC power output (PC terminal).
Check for short circuit on the inverter control terminals.
Sequence errors during use of the brake function.
See detailed explanation below
Too big speed deviation during vector control
Problem with the encoder signal
Occurs if there is a contact fault of the connector between
the inverter and the communication option or if the
communication option is fitted to connector 1 or 2 or if the
switch of the plug-in option is not on the default setting.
1 phase of the 3-ph input was lost for more than 1 second.
Repair the 3-phase power supply.
Overtemperature of motor PTC(switch AU/PTC must be on PTC)
1) Check if motor cooling fan (if present) functions
normally
2) check for contact faults in the wiring (see electrical
scheme)
Problem with parameter storage (EEPROM failure). If the
fault is persistent, replace the inverter.
Current exceeded the output current detection level
Resistor inrush current limit circuit overheated.
1) do not switch on/off the inverter frequently
2) Wait some time (15min) and try again
3) if the fault is persistent, replace the inverter
Communication problem on the RS485 terminals
connector
Overcurrent or overvoltage on input terminal 2/4
USB communication check time interval has elapsed
Speed exceeded the limit during encoder feedback control
Too big difference between the position command and the
position feedback during position control
PROGRAMMING MANUAL