FAILURE 95: WATCH DOG
If the watch dog has been activated, message 95 is logged in the Error log register. If this occurs often, ask
the help of a technician.
FAILURE 300-353: MITSUBISHI INVERTER ALARM MESSAGE
Always make sure you have the correct inverter parameter settings in the inverter, especially when you have
replaced an inverter. If you are not sure go to the Configuration menu and select „Inverter Menu...", set the
correct machine type and supply voltage and load the parameters from the wash computer to the inverter
once more. If the correct parameters are not in the inverter all kind of inverter alarms may occur. See also
inverter manual (available on request) for more info.
Err N°
Failure
Failure Name
300
Err OC1
Overcurrent
301
Err OC2
Overcurrent
302
Err OC3
Overcurrent
303
Err OV1
Overvoltage
304
Err OV2
Overvoltage
305
Err OV3
Overvoltage
306
Err THT
Inverter overload
307
Err THM
Motor overload
308
Err FAN
Fan stopped
309
Err OLT
Stall prevention
310
Err BE
Brake transistor
311
Err GF
Ground fault
312
Err OHT*
Ext thermal relay
313
Err OPT
Option
314
Err PE
Corrupt memory
315
Err PUE
PU leave out
316
Err Ret*
Retry no over
317
Err CPU
CPU Fault
318
Err E.6
CPU Fault 6
319
Err E.7
CPU Fault 7
320
Err IPF
Instantaneous
power failure
321
Err UVT
Under voltage
322
Err LF
Output phase
failure
323
Err OP1*
Option slot 1
324
Err OP2*
Option slot 2
325
Err OP3*
Option slot 3
540876_A_PUB_DATE_1_FEB_2012.DOC
Explanation
See detailed explanation below
See detailed explanation below
See detailed explanation below
See detailed explanation below
See detailed explanation below
See detailed explanation below
See detailed explanation below
See detailed explanation below
Repair the cooling fan (clean or replace if necessary)
See detailed explanation below
Short circuit in brake transistor circuit. Power off
immediately! Replace the inverter.
Output overcurrent to ground.
1) Check the motorcable and motor for ground faults.
2) Disconnect the motorcable and try again. If you still
have the error, replace the inverter.
External thermal relay (TRM module, see electrical
scheme) for motor protection tripped. TRM module was
only used on certain machines with MCB controller and
A500 inverter.
See detailed explanation below
Memory was overwritten too many times. Replace inverter.
See detailed explanation below
The max number of retries after fault reached.
The actual inverter error code that causes the problem and
which should be solved, is stored just before Err 316 in the
error log.
Communication error of built in CPU. Replace inverter
Internal fault, If the fault is persistent, replace the inverter
Internal fault, If the fault is persistent, replace the inverter
Power failure between 15 and 100ms. Check for bad
contacts in the power circuit. Repair the power supply.
Supply voltage too low. Check jumper P/+-P1.
Phase open detected on inverter output. Check for bad
contacts or defect (open) motor windings.
Problem with the option in slot 1 or option contact fault
Problem with the option in slot 2 or option contact fault
Problem with the option in slot 3 or option contact fault
PROGRAMMING MANUAL
TROUBLESHOOTING
93