4.6.2

Analog inputs

Labelling
X3/A1U
X3/A1I
X3/GA
4.6.3

Analog outputs

Labelling
X3/O1U
X3/AR
X3/GA
EDS84ASC552 EN 6.0
efesotomasyon.com - Lenze
Feature
Input
Input resistance
Input voltage in case of open circuit
Sampling frequency
Accuracy
Electric strength of external voltage
A/D converter
Input
Input resistance
Input current in case of open circuit
Sampling frequency
Accuracy
Electric strength of external voltage
A/D converter
GND, reference potential for analog signals
Features
Output voltage
Output current
Capacitive load
Voltage − 0 V
Output voltage at reset
Accuracy
Short−circuit strength
Electric strength of external voltage
Reference 10 V
Tolerance
Capacitive load
Short−circuit strength
Electric strength of external voltage
Permissible current loading
GND, reference potential for analog signals
l
Technical data
StateLine C control terminals
Analog inputs
Rated value
± 10 V
> 80 kW
Display "0" (U < 0.2 V, absolute)
1 kHz (1 ms)
± 0.1 V
± 15 V, permanent
Resolution 10 bits + sign
Error 1 digit º 0.1 % relating to the final value
0 ... +20 mA
4 ... +20 mA, fail−safe
215 W
Display "0" (I < 0.1 mA)
1 kHz (1 ms)
± 0.1 mA
± 7 V, permanent
10 bit resolution
Error 1 digit º 0.1 % relating to the final value
Rated value
0 ... 10 V
2 mA
max 1 mF
Display "0" (U < 0.1 V, absolute)
< 0.5 V
±2 % relating to the final value
Unlimited period
Not guaranteed
10.5 V
±0.5 V
max 1 mF
Unlimited period
Not guaranteed
10 mA
4
Parameterisable
55