5.3.3

Mounting in "cold plate" technique

The E84AVxxC... controllers are designed for assembly on coolers (e.g. collective coolers) in
"cold−plate" technique.
Requirements for collective coolers
The following items are important for the safe operation of the drive controllers:
Good thermal connection to the cooler
ƒ
– The contact area between the collective cooler and the drive controller must be at
least as big as the cooling plate of the drive controller.
– Even contact area, max. deviation 0.05mm.
– Connect the collective cooler with the drive controller with all the required
screwed joints.
Observe the thermal resistance R
ƒ
transmission between the cooler and the device. With a standard heat conducting
paste and a film thickness of 50 mm, it is approx. 0.03K/W. The values apply for the
operation of the drive controllers under rated conditions.
Type
E84AVxxC3024
E84AVxxC4024
E84AVxxC5524
E84AVxxC7524
E84AVxxC1134
E84AVxxC1534
EDS84ASC552 EN 6.0
efesotomasyon.com - Lenze
Mechanical installation
Standard devices in the power range 3 ... 22 kW
Mounting in "cold plate" technique
according to the table. The data includes the heat
th
Power to be dissipated
P
v [W]
115
155
215
250
355
390
l
5
Heatsink environment
R
[K/W]
th
£ 0.33
£ 0.25
£ 0.18
£ 0.15
£ 0.11
£ 0.10
79