Stateline C Control Terminals; External Supply Voltage 24 V - Lenze 8400 StateLine C Hardware Manual

L-force drives frequency inverter
Hide thumbs Also See for 8400 StateLine C:
Table of Contents

Advertisement

4
Technical data

StateLine C control terminals

External supply voltage 24 V

4.6
StateLine C control terminals
4.6.1
External supply voltage 24 V
Labelling
X4/24E
X4/GIO
Labelling
X4/24I
X4/GIO
54
efesotomasyon.com - Lenze
Feature
Connection for external 24 V supply
voltage by a safely separated
power supply unit (required for
mains−independent supply of the
control electronics and the
communication module)
Suppression of voltage pulses
Polarity reversal protection
Current consumption
Capacity to be charged
GND, reference potential for digital signals
Feature
24 V voltage output
to connect digital inputs via
potential−free contacts
Max. output current
Electric strength of external voltage
Excess current release
GND, reference potential for digital signals
l
Rated value
24 V in accordance with IEC 61131−2
19.2 ... 28.8 V
Residual ripple max. ± 5 %
SELV/PELV
Suppressor diode 36 V, bidirectional
When polarity is reversed: no function and no
destruction
Approx. 0.6 A during operation
Max. 1.5 A starting current for 100 ms
1000 mF
Rated value
External supply at 24E: voltage drop < 2.5 V
Internal supply: DC 18 ... 28 V
50 mA
+30 V
Automatically resettable
EDS84ASC552 EN 6.0