6
Electrical installation
Installation according to EMC (installation of a CE−typical drive system)

Mains connection, DC supply

6.2.2
Mains connection, DC supply
Controllers, mains chokes, or mains filters may only be connected to the mains via
ƒ
unshielded single cores or unshielded cables.
When a mains filter or RFI filter is used, shield the cable between mains filter or RFI
ƒ
filter and controller if its length exceeds 300 mm. Unshielded cores must be twisted.
In DC−bus operation or DC supply, use shielded cables.
ƒ
The cable cross−section must be dimensioned for the assigned fusing (observe
ƒ
national and regional regulations).