Technical data
Supply
The inputs and outputs are isolated and designed for a low−voltage supply through a safely
separated power supply unit (SELV/PELV) of 24 V DC. P/N switching input signals and test
pulses £ 1 ms are permissible.
Active sensors are directly wired to the X80 terminal strip.
Passive sensors are wired to the X80 terminal strip via a switching device. The switching
device must comply with the required control category of the application.
There is no monitoring for short circuits.
Detailed features of the inputs and outputs of the safety unit
Terminal
SIA, SIB
SIA
SIB
GI
24O, GO
DO
24O, GO, DO
Truth table
SIA
0
0
1
1
172
efesotomasyon.com - Lenze
Specification
Low signal
High signal
Input capacitance at switch−off
Input delay (tolerated test pulse)
Switch−off time (depending on the controller)
Running time
Input current
Input capacitance at switch−on, reduced
Input current
Input capacitance at switch−on, reduced
Ground for SIA/SIB
Supply voltage through safely separated power supply
unit (SELV/PELV)
Low signal
High signal
Output current
Inputs
Outputs
SIB
DO1
0
1
1
0
0
0
1
0
l
[Unit]
V
V
nF
ms
ms
ms
mA
mF
mA
mF
V
V
V
A
Description
"Safe torque off" is activated
Drive is active
min.
typ.
max.
−3
0
5
15
24
30
4
1
2.5
4
3
100
170
20
28
35
5
18
24
30
0
0.8
17
24
29
0.7
Enable
0
0
0
1
EDS84ASC552 EN 6.0