Mounting in "cold plate" technique

The E84AVxxC... controllers are designed for assembly on coolers (e.g. collective coolers) in
"cold−plate" technique.
Requirements for collective coolers
The following items are important for the safe operation of the drive controllers:
Good thermal connection to the cooler
ƒ
– The contact area between the collective cooler and the drive controller must be at
least as big as the cooling plate of the drive controller.
– Even contact area, max. deviation 0.05mm.
– Connect the collective cooler with the drive controller with all the required
screwed joints.
Observe the thermal resistance R
ƒ
transmission between the cooler and the device. With a standard heat conducting
paste and a film thickness of 50 mm, it is approx. 0.03K/W. The values apply for the
operation of the drive controllers under rated conditions.
Type
E84AVxxC2512
E84AVxxC3712
E84AVxxC5512
E84AVxxC7512
E84AVxxC1122
E84AVxxC1522
E84AVxxC2222
E84AVxxC3714
E84AVxxC5514
E84AVxxC7514
E84AVxxC1124
E84AVxxC1524
E84AVxxC2224
EDS84ASC552 EN 6.0
efesotomasyon.com - Lenze
Mechanical installation
Standard devices in the power range 0.25 ... 2.2 kW
Mounting in "cold plate" technique
according to the table. The data includes the heat
th
Power to be dissipated
P
v [W]
15
20
30
40
60
75
100
25
35
50
60
70
100
l
5
Heatsink environment
R
[K/W]
th
£ 1.5
£ 1.5
£ 1.0
£ 1.0
£ 0.6
£ 0.5
£ 0.4
£ 1.0
£ 1.0
£ 1.0
£ 0.6
£ 0.5
£ 0.4