6.7

HighLine C control terminals

6.7.1
External supply voltage 24 V
X5
Fig. 6−29
Labelling
24E
24I
GI
Terminal data
flexible
with wire end ferrule
EDS84ASC552 EN 6.0
efesotomasyon.com - Lenze
Connection to an external supply voltage
Description
Connection for an external 24 V supply by a safely separated power supply
unit (SELV/PELV), IEC 61131−2
(required for mains−independent supply of the control electronics and the communication
module)
Output 24 V, max. 50 mA
for connection of digital inputs via potential−free contacts
GND−I
Ground reference potential for the digital inputs
Conductor cross−section
2
[mm
]
0.2 ... 1.5
l
Electrical installation
HighLine C control terminals
External supply voltage 24 V
GND-I
X5
GI
DI7
DI6
DI5
DI4
8400HLC036
Tightening torque
[AWG]
[Nm]
24 ... 16
24 V int.
DI3
DI2
DI1
RFR
24I
24E
DC 24 V
S1
(+19.2...
+28.8 V)
8400HLC045
!
[lb−in]
2.5 x 0.4