7.2.2

Terminal control

Step−by−step commissioning
1. Wiring of power terminals
Make use of the Mounting Instructions supplied with the frequency inverter to wire the
power terminals according to the requirements of your device.
2. Wiring of control terminals.
– StateLine
Analog inputs at X3
X3
O1U GA A1I A1U AR
Wiring of the digital outputs at X4
X4
GIO
DO1
DI4
DI1 ... DI4: all active = High
– HighLine
Analog inputs at X3
X3
O2I
O2U
O1I
Wiring of the digital outputs at X5
X5
GI
DI7
DI6
3. If you can be sure that the frequency inverter is in the default state (Lenze setting),
you can skip the following step. If not, establish the Lenze setting of the frequency
inverter. We recommend to use the keypad for this.
)
Note!
The application "actuating drive speed" is implemented with the Lenze
setting.
EDS84ASC552 EN 6.0
efesotomasyon.com - Lenze
"
W
1k
...
W
10k
0...10 V
DI3
DI2
DI1
RFR
24I
24E
+
DC 24 V
_
O1U
GA
A2I
A2U
A1U
AR
A1I
"
1k
W
...
0 ... 10V
10k
W
DI5
DI4
DI3
DI2
DI1
RFR
24I
24E
DC 24 V
l
Commissioning
Quick commissioning
Terminal control
Assignment
Terminal control
A1U
Setpoint selection
10 V (=100 %):
1500 min
Assignment
Terminal control
l
RFR
Controller enable: RFR = High
l
Reset error:
High ® Low (edge−controlled)
DI1
Fixed frequency 1 ... fixed frequency 3, see
table below
DI2
DI3
DCB
DI4
Direction of rotation left/right (CCW/CW)
Assignment
Terminal control
A1U
Setpoint selection
10 V (=100 %):
1500 min
Assignment
Terminal control
l
RFR
Controller enable: RFR = High
l
Reset error:
High ® Low (edge−controlled)
−1
(with 4−pole motor)
−1
(with 4−pole motor)
147
7