Pre-Fault Setup - GE MOTOR MANAGEMENT RELAY 469 Instruction Manual

Table of Contents

Advertisement

4.14 S13 469 TESTING
S PRE-FAULT SETUP
S [ENTER] for more
4
The values entered under Pre-Fault Values will be substituted for the measured values in the 469 when the
simulation mode is "Simulate Pre-Fault".
4-84
ð
PRE-FAULT CURRENT
ENTER
PHASE A: 0.00 x CT
ESCAPE
PRE-FAULT CURRENT
ESCAPE
PHASE B: 0.00 x CT
MESSAGE
PRE-FAULT CURRENT
ESCAPE
PHASE C: 0.00 x CT
MESSAGE
PRE-FAULT GROUND
ESCAPE
CURRENT: 0.0 A
MESSAGE
PRE-FAULT VOLTAGES
ESCAPE
VLINE: 1.00 x RATED
MESSAGE
PRE-FAULT CURRENT
ESCAPE
LAGS VOLTAGE: 0°
MESSAGE
PRE-FAULT DIFF AMPS
ESCAPE
IDIFF: 0.00 x CT
MESSAGE
PRE-FAULT STATOR
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT BEARING
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT OTHER
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT AMBIENT
ESCAPE
RTD TEMP: 40°C
MESSAGE
PRE-FAULT SYSTEM
ESCAPE
FREQUENCY: 60.0 Hz
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 1: 0%
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 2: 0%
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 3: 0%
MESSAGE
PRE-FAULT ANALOG
ESCAPE
INPUT 4: 0%
MESSAGE
469 Motor Management Relay
4 SETPOINT PROGRAMMING

4.14.2 PRE-FAULT SETUP

Range: 0.00 to 20.00 x CT, step 0.01
Range: 0.00 to 20.00 x CT, step 0.01
Range: 0.00 to 20.00 x CT, step: 0.01
Range: 0.0 to 5000.0 A, step: 0.1
Range: 0.00 to 1.10 x RATED, step: 0.01
Range: 0 to 359°, step 1
Range: 0.00 to 1.10 x RATED, step 0.01
Range: –50 to 250°C, step 1
Range: –50 to 250°C, step 1
Range: –50 to 250°C, step 1
Range: –50 to 250°C, step 1
Range: 45.0 to 70.0 Hz, step 0.1
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
Range: 0 to 100%, step 1
GE Power Management