Environmental Specifications - IBM B01 Service Manual

Ibm s/390 integrated server 3006
Table of Contents

Advertisement

Figure 48. Table - Machine Area and Service Clearance
Machine Area (M2)
1
Machine Area (ft2)
1
0.6
6.0
Note:
1. Machine area includes installed covers.
Service Clearance Area
(M2) 2
3.4
Specifications.
Service Clearance Area
(ft2) 2
35.8
2. Service clearance area must be free of all obstacles. Units must be placed in a way that all service areas are
accessible. The weight distribution clearance area extending beyond the service clearance area, such as the area
at the outside corners of the units, may contain support walls and columns.
------------1
Airflow
Media and EPa Switch
762mm
(30 in)
This Side
1092mm
(43 in)
Cable
Entry/Exit Area
\r:
508mm
~
20in
762mm
t----Fr-o-nt-'-..........-'--..:i+-'--+--
(30 in) - - -
Top
View
Figure 49. Weight Distribution and Service Clearance
Environmental Specifications
Unless otherwise noted on individual specification pages, the following environmental specifications, based
on an altitude from sea level to 2134 meters (7000 feet), apply:
Environment
Operating
Nonoperating
Temperature
10°C-40°C (SO°F-104°F)
10°G-S2°C (SO°F-12S0F)
Rei Humidity
8%-80%
8%-80%
Max Wet Bulb
27°C (80°F) (Class C)
27°C (80°F)
Chapter 9. Power
213