IBM B01 Service Manual page 212

Ibm s/390 integrated server 3006
Table of Contents

Advertisement

3
For the OCA that has the LOAD FL T indicator ON,
exchange the following FRU:
• OCA
When complete, continue on step 37.
4
• Set the EPO switch on the front of the machine
to the off (down) position. Wait 10 seconds.
• Set the EPO switch back to the on position.
Wait 2 minutes.
Did the OCA indicators labelled LOAD FL T go
ON
again?
YES
NO
5
l
A short circuit has cleared and is no longer
present on the machine. A defective FRU
may indicate a logic fault. Wait for the
display panel to boot and check for errors.
Otherwise, call for assistance.
End of procedure
• Unfasten the PCI cage from the frame and
back the cage out about 7.5 mm (3 in.). Do not
unplug completely or remove any cables at this
point.
Push the button labelled PWR RESET on
BOTH OCAs
• Wait 2 minutes.
Is the fault cleared (LOAD FL T indicator
OFF
for
both OCAs)?
YES
NO
l
Continue on step 18.
Over
Current Isolation
For exchange procedures, see "OCA (Offline
Converter Assembly) Removal and Replacement"
on page 156.
For cage removal procedure, refer to "Adapter
110
Cage Assembly Removal and Replacement" on
page 162.
Chapter 9. Power
191