4.13.3.4. Program report configuration

The Report section allows you to configure archived vari-
ables such as DataLog and Batch Report.
Report (Page 1) allows you to configure the DataLog by
determining the information to be stored.
The available parameters are:
Sampling time: determines the sampling frequency.
The time interval between one sampling and the next
can vary from 1 to 3600 seconds.
Include recipes: includes the program recipe at the
top of the DataLog.
File name job no.: includes the production batch num-
ber in the file name.
Encrypted file: apply encryption to the DataLog file.
The file can be decrypted with the DataLog Utility
application.
Comma : dot format: use the dot as the separation
between the integer and the decimal part of the num-
bers.
Sampled variables - Group: allows you to select the
variables to be sampled and assign them to a group,
so that they can be viewed in the DataLog Utility appli-
cation.
Assign the same group to homogeneous variables.
Touch the variable field to open a window pop-up to
select the variable. For details on the pop-up window,
see the description on page 103, while to find out
about management of saving on different media
on page 47
Report (page 2) allows you to include segments from digital
variables in the event report and to associate a descriptive
text for each event. In the report, events are listed after
sampling. The available parameters are:
Variable: lets you select digital variables.
Touch the variable field to open a window pop-up to
select the variable.
80703B_MHW_2850T/3850T_02-2019_ENG
For details on the pop-up window, see the description
on page 103.
String: lets you select a stored text string.
For details on the pop-up window, see the description
on page 103.

4.13.4. Read from disk sub-menu

In order to use this submenu you should be level 1 or 0,
depending on the instrument configuration. The visibility of
the reading button may be conditioned by parameters in
page x850 SETUP\CFG 2.
Opens a pop-up window that lists all programs stored on
the disk. For details on the pop-up window, see the de-
scription on page 103.

4.13.5. New prog sub-menu

In order to use this submenu you should be level 1 or 0,
depending on the instrument configuration.
The available parameters are:
Program name: touch the field to open the virtual
keyboard to enter the program name. The name can be
up to 16 characters long and must be unique.
Number: the program ID number. It is automatically
generated by the system and can not be modified.
Enable double step: the double step is a segment
composed of a ramp and a retention; if double step is
disabled, each ramp and each retention will constitute
a single segment created independently.
Double step
example
7
Single step
Step
example
1
7
The Save button appears when a name is attributed to a
program and is used to create the new program. Saving the
program opens page 1 in the program configuration Base
section. To continue see instructions on page 105 and
subsequent.
The Cancel button closes the window without saving the
changes made.
4. CONFIGURATION
Step 1: ramp 2 s +
hold 2 s
Step 2: ramp 2 s +
Step
Step
hold 0 s
1
2
9
11
12
Step 1: ramp 2 s
Step 2: hold 2 s
Step
Step
Step 3: ramp 2 s
2
3
9
11
12
s
s
69