10. TECHNICAL SPECIFICATIONS
GETLogic
DATA LOGGER
PRODUCTION REPORT
(Batch report)
140
Scope
Running sequences
Function blocks
Logic function blocks
Timer function blocks
Counter function blocks
Basic mathematical func-
tion blocks
Special mathematical
function blocks
Special mathematical
function blocks
Process function blocks
Resources for mathemat-
ics operators
Resources for logical
operators
Scope
Recordable values
Sampling
Data storage
Graphic display
Scope
Recordable values
Sampling
Data storage
Graphic display
Sequential execution of logical and mathematical instructions
1 for each program (max 4) + 1 global always active
Max number per program: 200
AND, OR with default logic patterns
Set/Reset, Reset/Set
Rising edge, trailing edge
Excitation delay timer (TON)
De-energising delay timer (TOFF)
Flip/flop timer
Increasing counter
Decreasing counter
+ , - , × , : , average, minimum value, maximum value, square
root, base 10 logarithm, natural base A logarithm, and raised to
the power A, A raised to the power B
Max peak, minimum peak, hold of a value, average of 2 values,
minimum/maximum limit of a value
Selection between two values Greater/Lesser/Equal/Great-
er-Equal/Lesser-Equal/Different
F0 (sterilisation coefficient)
Analog IN/OUT, SP controller, System Log/Real data
Digital In/Out, Alarm Status, System Merker
Continuous configured data recording
Max number of analog values: 25
Max number of digital events: 50
Sampling interval: 1 s ... 1 h
Sampling mode: single record with time information (date/time)
and values /events/actions detected
Closing the sequential log file: automatic every hour/day/week
(configurable)
File format: CSV
Data file encryption: optional
Log file name with close date/time indication
Storage media: internal memory
File export: manual via USB key or manual/automatic via Ether-
net via Gefran - DataLog Utility PC application
- Report Utility
Graph: stored log data trend
Max number of viewable curves: 8
Data selection by association: 8 curves
Single curve scaling
Available functions: enable single curve, full scale selection,
zoom +/-, scroll +/- and cursor
Synchronous recording when running the program profile
Max number of analog values: 25
Max number of digital events: 50
Batch name/description (selectable)
Running profile data (selectable)
Sampling interval: 1 s ... 1 h
Sampling mode: single record with time information (date/time)
and values /events/actions detected
File format: CSV
Data file encryption: optional
Log file name with close date/time indication and Job ID refer-
ence (optional)
Storage media: internal memory
File export: manual via USB key or manual/automatic via Ether-
net via Gefran - DataLog Utility PC application
- Report Utility
Graph: stored log data trend
Max number of viewable curves: 8
Data selection by page: 8 curves
Single curve scaling
Available functions: enable single curve, full scale selection,
zoom +/-, scroll +/- and cursor