10.3. F-GCANs communications module

GENERAL DATA
VOLTAGE
CONNECTIONS
SIGNAL ELEMENTS
ENVIRONMENTAL CONDI-
TIONS
PROTECTION RATING
ASSEMBLY
DIMENSIONS
WEIGHT
EC REGULATIONS
UL REGULATIONS
80703B_MHW_2850T/3850T_02-2019_ENG
Operating voltage
Current absorption
Dissipated power
Connection
CAN
Error
Running
Voltage
Indoor
Operating temperature
Storage temperature
Relative humidity
Positioning
Mount
(L × H × D)
EMC conformity
(electromagnetic
compatibility)
10. TECHNICAL SPECIFICATIONS
24 VDC ±25%
2 A max
2.5 W
Polarised connector with spring terminals,
cable 1 mm
(0.0015 in2) (17 AWG) max
2
Connector: DB9
Protocol: CANopen 2.0B, level CAN DS301 v.3.0, v4.0
Red LED
Green LED
Yellow LED
Use
0 ... +55 °C (32.... 131 °F)
-20 ... +70 °C (-4 .... 158 °F)
max 95% RH non-condensing
IP20
Vertical
On DIN 35 mm (1.38") rail
25.4 × 92 × 90 mm (1" x 3.62" x 3.54")
0.15 kg (0.33 lb)
Compliance with the 2014/30/EU Directive
EMC Emission: EN 61000-6-4
EMC Immunity: EN 61131-2, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-6, EN 61000-4-8, EN 61000-4-11
Compliance with UL508 standard