Practical configuration examples

7.7.1.

Loop configuration

The example describes the procedure for configuring a PID
with the following features:
Heat/Cool action;
K thermocouple input;
digital control output with Heat/Cool action;
2 absolute Maximum and Minimum alarms.
For the configuration of the PID, the following variables
(signals) of the F-MIX module are used:
Type
Name
Analog input (AI1)
Digital Output
(DO1)
Digital Output
(DO2)
Digital Output
(DO3)
Digital Output
(DO4)
To configure the PID loop, proceed as follows:
1.
Login with level 2 password.
Select SETUP.
2.
80703B_MHW_2850T/3850T_02-2019_ENG
Description
AI_01
Input signal 1
Digital output 1 -
DO_01
Heat action
Digital output 2 -
DO_02
Cool action
Digital output 3 -
DO_03
HIGH alarm
Digital output 4 -
DO_04
LOW alarm
7. EXAMPLES AND APPLICATION NOTES
Select HW CFG.
3.
4.
Select module F_MIX.
5.
Configure the type of thermocouple associated with
channel 1 (AI1) of the F-MIX module.
Touch IN1 Type and select TC_K (K thermocouple).
The default variable associated with the temperature
value of channel 1 is AI_01.
113