gefran 3850T Use And Installation Manual page 147

Multi-purpose controller
Table of Contents

Advertisement

GETLogic
DATA LOGGER
PRODUCTION REPORT
(Batch report)
80703B_MHW_2850T/3850T_02-2019_ENG
Scope
Running sequences
Function blocks
Logic function blocks
Timer function blocks
Counter function blocks
Basic mathematical function
blocks
Special mathematical function
blocks
Special mathematical function
blocks
Process function blocks
Resources for mathematics
operators
Resources for logical opera-
tors
Scope
Recordable values
Sampling
Data storage
Graphic display
Scope
Recordable values
Sampling
Data storage
Graphic display
10. TECHNICAL SPECIFICATIONS
Sequential execution of logical and mathematical instruc-
tions
1 for each program (max 8) + 1 global always active
Max number per program: 200
AND, OR with default logic patterns
Set/Reset, Reset/Set
Rising edge, trailing edge
Excitation delay timer (TON)
De-energising delay timer (TOFF)
Flip/flop timer
Increasing counter
Decreasing counter
+ , - , × , : , average, minimum value, maximum value,
square root, base 10 logarithm, natural base A logarithm,
and raised to the power A, A raised to the power B
Max peak, minimum peak, hold of a value, average of 2
values, minimum/maximum limit of a value
Selection between two values Greater/Lesser/Equal/
Greater-Equal/Lesser-Equal/Different
F0 (sterilisation coefficient)
Analog IN/OUT, SP controller, System Log/Real data
Digital In/Out, Alarm Status, System Merker
Continuous configured data recording
Max number of analog values: 50
Max number of digital events: 50
Sampling interval: 1 s ... 1 h
Sampling mode: single record with time information (date/
time) and values /events/actions detected
Closing the sequential log file: automatic every hour/day/
week (configurable)
File format: CSV
Data file encryption: optional
Log file name with close date/time indication
Storage media: internal memory
File export: manual via USB key or manual/automatic via
Ethernet via Gefran - DataLog Utility PC application
- Report Utility
Graph: stored log data trend
Max number of viewable curves: 8
Data selection by association: 8 curves
Single curve scaling
Available functions: enable single curve, full scale selec-
tion, zoom +/-, scroll +/- and cursor
Synchronous recording when running the program profile
Max number of analog values: 50
Max number of digital events: 50
Batch name/description (selectable)
Running profile data (selectable)
Sampling interval: 1 s ... 1 h
Sampling mode: single record with time information (date/
time) and values /events/actions detected
File format: CSV
Data file encryption: optional
Log file name with close date/time indication and Job ID
reference (optional)
Storage media: internal memory
File export: manual via USB key or manual/automatic via
Ethernet via Gefran - DataLog Utility PC application
- Report Utility
Graph: stored log data trend
Max number of viewable curves: 8
Data selection by page: 8 curves
Single curve scaling
Available functions: enable single curve, full scale selec-
tion, zoom +/-, scroll +/- and cursor
145

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2850t

Table of Contents