● DP master, not isochronous
● MPI interface
Both PROFIBUS DP interfaces are set by default for operation as master at address 2 at a
transmission rate of 1.5 Mbit/s. The PROFIBUS DP network is automatically detected and
generated for this setting.
However, you can select other settings. Such user-specific settings must be configured in HW
Config and NetPro.
Note
Communication with the SINAMICS Integrated of a D410 is always equidistant. Here, the
SIMOTION D410 is the master and the SINAMICS Integrated drive is the slave.
4.3.4

Creating a new PROFIBUS DP subnet

The SIMOTION D410 device is networked using SIMOTION SCOUT. Set up your user-specific
bus parameters for the PROFIBUS interface when you configure the network.
Note
The actions outlined below only need to be taken if you have not selected an interface when
integrating the SIMOTION D410 into the project (refer to section Creating a project and
configuring the communication (Page 53)).
Next the connection to the PG/PC must be established via NetPro, refer to:
● Section Configuring the PROFIBUS PG/PC interface (only for D410 DP) (Page 56)
● Section Configuring the Ethernet PG/PC interface (only for D410 PN) (Page 58).
1. Double-click the "D410" entry in the Project Navigator in order to open HW Config.
2. Double-click the DP/MPI interface in the SIMOTION D410 representation in HW Config.
3. Click "Properties" in the "General" tab to open the "PROFIBUS interface DP/MPI" dialog
4. Click "New" to open the "Properties - New PROFIBUS Subnet" dialog box.
5. Name the new subnet, and then enter its properties in the "Network settings" tab, for
6. Click "OK" to accept the settings.
7. Save and compile the changes.
The PROFIBUS subnet you created is displayed as a graphic object in HW Config.
SIMOTION D410
Commissioning Manual, 04/2014
The "Properties - DP/MPI" dialog box opens.
box.
example, the transmission rate.
The new subnet is now displayed in the "Properties - PROFIBUS interface DP/MPI" dialog
box and is ready for being interconnected with the PROFIBUS DP interface.
4.3 Configuring the PROFIBUS DP interface (only D410 DP)
Parameter assignment / addressing
63