Maintenance and service
6.2 Replacing modules (spare part scenario)
See also
Update via CF card (Page 191)
6.2.4

Replacing the fan

Requirement
Replace the fan if a warning is output by the temperature monitoring function as a result of a
fan defect.
The SIMOTION D410 fans switch on depending on the internal module temperature. If the
temperature reaches impermissible values, this is signaled by a warning at the drive end:
A1009: CU warning: Control Unit overtemperature
In this case, the temperature (CU parameter r0037[0]) of the SIMOTION D410 has exceeded
the specified limit value.
Remedy:
● Check the supply air for the SIMOTION D410.
● Check the fan for the SIMOTION D410.
The warning will automatically disappear as soon as the limit value is undershot.
If the fan is defective, it must be replaced.
The fan can be ordered as spare part, see "Spare parts and accessories" in the
SIMOTION D410 Manual.
NOTICE
Damage to the module due to improper intervention
Fan replacement on the SIMOTION D410 must only be performed by qualified personnel!
● De-energize the module before you start any work.
● Use a flat-bladed screwdriver with a very thin blade.
● Proceed carefully to avoid damaging the plastic housing.
● Avoid making contact with the printed circuit board.
● Observe ESD guidelines, see Section ESD guidelines (Page 221).
172
– Does the control cabinet temperature fall within the permitted range?
– Is natural convection possible?
– Is the fan failing to rotate, despite the warning?
– Is the fan blocked by dirt/foreign bodies?
SIMOTION D410
Commissioning Manual, 04/2014