3 Settings, MPI / OPI
3.7

Customer operator panel interface

3.7
Customer operator panel interface
Interface
Location of the
interfaces
Switch S3, default
setting
Power
supply
interface
3-68
A customer operator panel can be connected via the interface. 64 digital inputs
and 64 digital outputs with C-MOS level (5 V) are available on the module for
this purpose.
The module must have firmware version V 03_01_01 or higher.
64.7
X20
MPI connection
Equipotential bonding connection
X10
ON
"
S3
7.2
Fig. 3-12
Front view of interface to customer operator panel
If only the customer operator panel is to be connected, then the bus address
must be set to 6 as for the MCP (standard application).
Table 3-9
Setting for 840D: Switch S3 on interface for customer operator panel
1
2
3
4
5
on
off
on
off
on
Connector designation:
Connector type:
Table 3-10
Pin assignment of X10 connector on interface to customer operator panel
Pin
1
2
3
SINUMERIK 840D Installation and Start-Up Guide (IAD) – 04.00 Edition
289.4
X211
Holes 3.6
207.3
6
7
8
on
off
on
Baud rate: 1.5 Mbaud (OPI)
Cyclical transmit pattern: 100 ms
Bus address: 6
X10
3-pin Phoenix terminal block, straight
X10
Name
SHIELD
M24
P24
 Siemens AG 2000 All Rights Reserved
08.97
03.96
X221
X231
92.7
H3
H1
3.5
LEDs
H4
H2
Meaning:
Type
VI
VI
VI