6.4.4

Operation with operator panel

6.4.4.1

"Operator panel available" parameter

With the "Operator panel available" parameter, you determine whether or not an operator
panel is available for operating the compact starters.
In conjunction with the "Operation at Preset <> Actual Configuration" parameter, operation of
the compact starters with or without operator panel can be configured (see Chapter
"Parameter "Operation at Preset <> Actual Configuration" (Page 109)").
Use of the operator panel is above all useful if manual intervention in an application is an
indispensable requirement for operating the plant, or to enable manual intervention in an
emergency.
The table below shows the values for the "Operator panel available" parameter.
Table 6- 4
Value
0
1
The "Operator panel available" parameter can only be modified via IO-Link. It cannot be
adjusted at the device.
6.4.4.2
Parameter "Operation at Preset <> Actual Configuration"
The "Operation at Preset <> Actual Configuration" parameter sets the severity level of the
test for the "Operator panel available" parameter.
The table below shows the values for the "Operation at Preset <> Actual Configuration"
parameter.
Table 6- 5
Value
0
1
If the parameter value "Operation at Preset <> Actual Configuration" is set to "disable",
operation of the compact starters is only possible if the parameter setting "Operator panel
available" is fulfilled precisely.
If the parameter value "Operation at Preset <> Actual Configuration" is set to "enable",
operation of the compact starters is possible via IO-Link regardless of whether or not an
operator panel is connected.
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
"Operator panel available" parameter
Description
Operator panel available: No
Operator panel available: Yes
Parameter "Operation at Preset <> Actual Configuration"
Description
Operation at Preset <> Actual Configuration: disable
Operation at Preset <> Actual Configuration: enable
3RA64/3RA65 compact starter with IO-Link
Default setting
Yes
Default setting
enabled
6.4 Parameters
109