11 Data Backup
11.7 Data backup with VALITEK streamer on the MMC101/102/103 (SW 5.3 and lower)
11.7
Data backup with VALITEK streamer on the
MMC101/102/103 (SW 5.3 and lower)
What can you back
up?
Streamer
connection
Operator action
11-276
With the VALITEK streamer you can:
S
Back up all the data on hard disk C (back up all)
S
Back up the user data (archive format) in directory C:\DH\ARC.DIR (backup
user data)
S
Restore the data backup (restore from tape)
The VALITEK streamer is connected to parallel interface X8 (25-pin) on MMC
101/102/103. Siemens cable 6FC9 344–4xV must be used to make the link.
You cannot connect any other type of data backup device because the software
is adapted especially to the VALITEK streamer.
During MMC power-up (after control has been switched on)
while the message Starting MS DOS is displayed:
1. Press key 6 on the operator panel keyboard just once and briefly.
The following menu is displayed:
PLEASE SELECT:
1 Install/Update MMC System
2 MMC Configuration Tool
3 DOS Shell
4 Start Windows (Service Mode)
5 MMC System Check
6 Reboot System (Warmboot)
7 Backup / Restore
8 Start PC Link
9 End (Load MMC)
Your Choice [1,2,3,4,5,6,7,8]?
2. Press key 7
The system requests you to enter a password with:
passwd:
3. Enter a password for levels 0 – 2.
– System
– Manufacturer
– Service
The following menu is displayed:
SINUMERIK 840D Installation and Start-Up Guide (IAD) – 04.00 Edition
 Siemens AG 2000 All Rights Reserved
12.98
03.96