11.6.10 Step 10, change the indication mode on the operator interface
Change the indication of the blocking states
Select
Option
Function
1 (default)
KEY13
Indication mode "Standard":
▼
–
LED 3 = not used
LED 4 = "Manual only"
–
–
LED 5 = "Autom. & Man. blocked"
2
Indication mode "Alternative":
–
LED 3 = "Manual only"
–
LED 4 = "Autom. & Man." (normal)
LED 5 = "Autom. & Man. blocked"
–
Change the active mode of indicator "Released" (LED8)
Select
Option
Function
KEY14
3 (default)
Flashing when activated
▼
4
Always in steady mode when activated
11.6.11 Step 11, change the function of the detector zones 1 to 3
Change the function of the detector zones 1 and 2
Select
Option
Function
KEY13
"Alarm" zone 1 and zone 2 = "Activated"
1 (default)
▼
"Alarm" zone 1 or zone 2
"Alarm" zone 1
2
"Alarm" zone 2
Same as option 2 but functions "Enable/Disable Zones" and
3
"Enable/Disable Detector test" suppressed
4
"Alarm" zone 1 or zone 2
5
Zone 1 and zone 2 not used
Change the line fault processing of the detector zones 1 and 2
Select
Option
Function
KEY14
6 (default)
Line open and line short circuit
▼
7
Line open
8
Line short circuit
Change the function of the detector zone 3
Select
Option
Function
KEY15
"Alarm" zone 3 = Activate fire control lines, RT-alarm (if option 3 or 4
▼
9 (default)
10
"Alarm" zone 3 = Activate LED6, horn lines
11
Zone 3 not used
"Alarm" zone 1 + 2 + 3 = "Activated"
12
"Alarm" zone 1 or 2 or 3 or any two zones = "Fire alarm"
"Alarm" zone 3 = Activate fire control lines, LED6, horn lines
13
Processing as "Air sampling system" (earliest warning)
Building Technologies
Fire Safety & Security Products
= "Fire alarm"
= "Fire alarm"
= "Activated"
= "Activated"
= "Fault"
= "Alarm"
= "Alarm"
programmed in step 3), LED6, horn lines, fire
alarm outputs
Programming the user functions
Zone 1
Zone 2
Zone 3
Red
Yel. Red Yel. Red Yel. Red Yel.
–
Zone 1
Zone 2
Zone 3
Red
Yel.
Red
Yel. Red Yel. Red Yel.
–
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red Yel. Red Yel.
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Zone 1
Zone 2
Zone 3
Red Yel. Red
Yel.
Red Yel.
–
–
–
–
Zone 1
Zone 2
Zone 3
Red Yel. Red
Yel. Red Yel.
A6V10099837_a_en
Zone 4
Zone 4
Zone 4
Zone 4
Red Yel.
Zone 4
Red Yel.
–
–
–
–