4 Mechanical and electrical installation

Limitations of the modules' data exchange rates

Introduction
Evaluation of input and
output factors
98
There are two options for connecting remote peripheral modules: via
JX3-BN-CAN using the JX2 system bus protocol, or via JX3-BN-ETH using
the Ethernet system bus protocol. JX3 modules of a JX3 station exchange
data either with a JC-120MC controller, or with bus node modules
JX3-BN-CAN and JX3-BN-ETH. The maximum number of input and output
data and of JX3 peripheral modules in a JX3 system is limited.
The following table lists the factors for input and output data.
Add the input factor of all modules used and calculate the aggregated input
factor.
Add the output factor of all modules used and calculate the aggregated
output factor.
Compare the aggregated factor for inputs/outputs with the allowed
maximum factor:
where n <= 16.
Peripheral module
JX3-AI4
JX3-AO4
JX3-CNT
JX3-DI16
JX3-DIO16
JX3-DMS2
JX3-DO16
JX3-MIX1
JX3-MIX2
JX3-THI2-RTD
JX3-THI2-TC
Input factor per module
10
2
10
4
4
10
2
16
16
10
10
Output factor per module
0
8
0
0
2
0
2
6
6
0
0