JC-120MC
Effect
Related topics
Jetter AG
Important note:
The EEPROM data on the backplane module allow for 100,000 write cycles.
We urgently recommend the following workflow:
First read out the value, then compare it. Only if the value has changed, start
writing.
Write to register 101299 to have the controller take the following steps:
The controller creates a configuration file out of the values.
It saves the configuration file to the backplane module as
/System/config.ini.
If you have entered comments and formatting details into this file, the
comments and formatting details will get lost during this process.
The configuration memory (see page 75)
Setting the IP address during runtime (see page 88)
Setting the IP address via configuration file (see page 83)
Setting the IP address via configuration file and DIP switch (see
page 84)
Mechanical and electrical installation
87