Jetter JC-120MC User Manual page 289

Table of Contents

Advertisement

JC-120MC
System command 123
System command 160
System command 161
System command 170
Jetter AG
Activate - Wait for communication
Effect:
The controller cyclically checks for communication requests from external
partners for 1 to 2 ms.
Advantage:
External communication partners get a faster reply from the controller.
Disadvantage:
Application program processing takes slightly longer.
Deactivate - Task switch on I/O access
Effect:
While the controller is accessing modules on the JX2 or JX3 system bus,
other tasks of the application program are not processed.
Advantage:
The controller executes I/O accesses as fast as possible.
Disadvantage:
As certain I/O accesses are significantly slower than access to internal
variables, response time of other tasks may increase.
Activate - Task switch on I/O access
Effect:
While the controller is accessing modules on the JX2 or JX3 system bus, it
processes the other tasks of the application program.
Advantage:
The execution time of certain I/O accesses which may be relatively long does
not affect the response time of other tasks.
Disadvantage:
The run time of the other tasks influences the execution time of several
I/O accesses.
Deactivate - Resume task time slot
Effect:
When a normal application task has been interrupted by a cyclic task or the
Ethernet system bus publisher, processing the following application task is
resumed. The remaining time of the time slot of the interrupted task lapses for
one cycle.