Meaning Of The Leds On The S120 Combi - Siemens SINAMICS S120 Combi Equipment Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

S120 Combi Power Modules
3.3 Interface description
3.3.11

Meaning of the LEDs on the S120 Combi

The SINAMICS S120 Combi has two LEDs to display the status of the components. The
software assigns a priority to the status signals from the individual components. The most
important and/or most informative status is output for the complete S120 Combi.
The status is immediately output if any component develops a fault. The ready to run
indication is only issued if all of the components have signaled that they are ready to run.
The LED statuses for the S120 Combi are described in the table below. The status display
always refers to the complete S120 Combi.
Table 3- 16
Meaning of the LEDs on the S120 Combi
Status
READY
DC LINK
Off
Off
Green
Off
Orange
Red
Orange
Orange
Red
-
Green/Red
-
(0.5 Hz)
Green/Red
-
(2 Hz)
Green/Orange
-
or
Red/Orange
Hazardous DC link voltages may be present at any time regardless of the status of the "DC
link" LED.
The warning information on the components must be carefully observed!
88
Description, cause
Electronics power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
The LED is activated irrespective of whether the corresponding
messages have been reconfigured.
Firmware is being downloaded.
Firmware has been downloaded.
Wait for POWER ON.
Component recognition via LED is activated (p0124).
Note:
Both options depend on the LED status when component
recognition is activated via p0124 = 1.
WARNING
Remedy
Connect/test the electronics
power supply
-
-
Check the line supply
voltage.
-
Remedy and acknowledge
fault
Carry out a POWER ON
-
SINAMICS S120 Combi
Manual, Edition 05.2010, 6SL3097-4AV00-0BP0