7.2

Module Parameter

This section describes the "Module parameter" window of the GX Works3.
[Navigation window]  [Parameter]  [Module Information]  [FX5-DP-M]  [Module Parameter]
Name
Item
Basic
Consistency
setting
Application
CPU Error Output Mode
setting
Setting
Refresh
Refresh Timing
setting
Refresh Group
Precautions
After the "Module Parameter" screen is displayed, make sure to update the PROFIBUS labels. (
PROFIBUS Labels)
Description
Sets the I/O data exchange method. ( Page 35 Data Consistency Function)
• Disable: Disables the data consistency function.
• Enable (Use Autorefresh): Enables the data consistency function.
Configure the refresh settings of "Master Settings" under "Setup Tasks" in the
"PROFIBUS Configurator Tasks" window. ( Page 58 Setup Tasks)
Sets the FX5-DP-M status when a CPU module stop error occurs. ( Page 37
Output Setting Function for CPU Stop Error)
■Clear
• The data exchange with DP-Slaves are interrupted.
• The output data in the buffer memory of the FX5-DP-M are cleared and not sent.
• When the CPU module stop error occurs, the input data received from DP-Slaves
are held in the buffer memory of the FX5-DP-M.
■Hold
• The data exchange with DP-Slaves are continued.
• The output data in the buffer memory of the FX5-DP-M are held when the CPU
module stop error occurs and then sends the data to the DP-Slaves.
• The input data received from DP-Slaves are updated into the buffer memory of the
FX5-DP-M.
Sets the refresh timing.
Specifies the refresh group of the program.
Setting
• Disable
• Enable (Use
Autorefresh)
(Default: Disable)
• Clear
• Hold
(Default: Clear)
At the Execution Time of
END Instruction (fixed)
1 (fixed)
Page 50 Update of
7 PARAMETER SETTINGS
7.2 Module Parameter
7
49