Modbus/Tcp (P/N1295-0520; Configuring The Ip Address - Honeywell Vertex M Technical Handbook

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

Vertex M
24-Point Continuous Monitor
TM
Function
Alarms
Faults
Concentrations
Heartbeat
A.11 Modbus/TCP (P/N1295-0520)
Modbus/TCP provides the highly reliable communications
like the other fieldbusses over fast, economical Ethernet
media. This interface uses ProSoft-Technology MVI46-
MNET hardware. In the Vertex M, this interface is always
a TCP server, never a client. For more information see
www.prosoft-technology.com
The 122 words of status information listed in
A-5
are mapped as Modbus holding registers 40001
to 40122.
Appendix A - Network Interface and Options
Table A-9. LonWorks Network Variable Outputs
Names
nvoAlm_1_1_1
to nvoAlm_3_3_8
nvoFlt_1_1
to nvoFlt_3_3
nvoConc_1_1_1 to nvoConc_3_3_8 SNVT_count
nvoHeartbeat
and www.modbus.org.
Table
SNVT_lev_disc
SNVT_lev_disc
SNVT_count
A.11.1 Configuring the IP Address
The following resources are needed to needed to set
the IP address of the Vertex M.
1. An external personal computer with Microsoft
Windows 2000 or later operating system and
an unused serial port.
2. The debugging cable shown in
3. The file "WATTCP.CFG". This may be supplied
on a floppy disk or may be loaded in "C:\hmi\
FieldbusFiles"
Figure A-5. Debugging Cable
F-17
Type
Number
72
9
72
1
Figure
A-5.