Honeywell Vertex M Technical Handbook page 156

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

Event
Event List
Number
Desc. (Short)
241
OPT REF ADJ
TIMEOUT
270
COM AZ # #
BROKEN
301
PLC-COM
BROKEN
302
AZ-BAD PROF
ID
303
PLC-BAD
PROF ID
304
PLC SYSTEM
FAULT
305
DATA LOG
FAILED
413
CMD ERR AZ
#-#
Section 6 - Troubleshooting
Event History
Data Field
Description
Optics reference
Error code
adjustment
timeout
OPC To Az ##
Communica-tions
Broken
PLC-Com
Broken
AZ has wrong
profile loaded
PLC Has Wrong
Profile loaded
PLC System
PLC Error
Fault
Code
Unable To Log
Conc Data
Cmd Error Az #-#
Problem
Optics block self-
adjustment timeout.
Analyzer not
Analyzer powered down
responding to OPC
driver polling request
Ethernet cable not
connected
PLC fails to respond to
Cable connection
DAq communication
problem
Loss of PLC power
Profile ID in analyzer
Configuration not properly
does not match current
loaded
configuration in use
Profile ID in PLC does
Configuration not properly
not match current
loaded
configuration in use
A fault has occurred on
Faulty or missing PLC
the PLC that prevents
module
the PLC program from
PLC is not properly
running
configured
Failure to store
Local database file has
concentration data in
reached size limit (1GB
the database
maximum size for Access
database).
Analyzer not
Cable connections
responding DAq
Communica-tions
Analyzer missing or
powered down
6-16
Possible Cause
Cycle power to analyzer.
Contact Honeywell service.
Check switch on power
module
Check Ethernet
connection at the back of
the analyzer
Move cable to different
port on Ethernet hub
Check serial
communications on DAq
COM2
Check serial cable on
PLC 1747-KE
See
Section 1.2.7 Data
Acquisition Computer
(rear)
See
Section 1.2.9 Main
PLC
Check power connections
for PLC
Reinstall current
Configuration Profile
Reinstall current
Configuration Profile
Contact Honeywell
Analytics Service
Enable automatic
database purge or adjust
database purge settings
to purge old data
Check Ethernet
connections
Remove analyzer from
Configuration Profile
Recovery

Advertisement

Table of Contents
loading

Table of Contents