A.8 DF1 Interface (P/N1295-0343)
This module emulates the DF1 slave functionality of
an Allen-Bradley SLC 5/03 DF1 port. It responds to
queries for data from the N14 integer file by sending
alarm, fault, and concentration data.
The DF1 protocol is defined by the Allen-Bradley
DF1 Protocol and Command Set Reference Manual
which can be downloaded from
rockwellautomation.com/idc/groups/literature/
documents/rm/1770-rm516_-en-p.pdf.
Technical information on the ProSoft Technology
MVI46-DFCM interface which is used in the Vertex M
can be found at http://www.prosoft-technology.com.
The baud rate and address of the DF1 interface are
set using the configuration profile utility as described
in See
Section 3.6 Configuration
speeds range from 1200 to 57,600 baud with a default
of 19,200. The DF1 address can be set from 2 to 127.
The data map used by the DF1 interface is shown
in
Table
A-5. This appears as the N14 file. The
interpretation of the data is in
Appendix A - Network Interface and Options
http://literature.
Utility. Supported
Table A-3
and
Table
A-4.
Figure A-4. DF1 Connection to RJ45 Socket
The pinout of the DF1 port is as follows:
Table A-8. Pinout of DF1 Port
RS-232
RJ45
DB-9
mode pin
Pin
Pin
function
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
F-15
DF1
connection
is made to
middle RJ45
socket
RS-422
mode pin
function
TxD+
RxD
RxD+
TxD
GND
GND
RxD-
RTS
CTS
TxD-
RS-485
mode pin
function
TxD/RxD+
GND
TxD/RxD-