Honeywell Vertex M Technical Handbook page 204

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

Vertex M
24-Point Continuous Monitor
TM
Folder
Tag Count
72
Fault
1
1
MonStat
72
Appendix A - Network Interface and Options
Table F-3. Tag Names (continued)
Recommended
Tag Name
for most HMI
Format
systems
Y
##
Y
HMI
Y
PLC
Y
##
Value Interpretation / Description
Unsigned integer
Status
0 = No fault
1 = Maintenance Fault
2 = Instrument Fault
3 = Both
Reports only point-specific faults
Unsigned integer
Status
0 = No fault
1 = Maintenance Fault
2 = Instrument Fault
3 = Both
Reports only faults originating in the HMI
Unsigned integer, Indicates the presence of a fault for the PLC
Status
0 = No fault
1 = Maintenance Fault
2 = Instrument Fault
3 = Both
Indicates the presence of a fault originating in the PLC.
Integer, 1 byte long, interpreted as a bitmask. This reports status for point
as listed below:
bits 0-2 - run alarm disable status as a 3-bit integer
0 = no data
1 = Point enabled
2 = RunTimeAlarmDisable Relays only
3 = RunTimeAlarmDisable Full (No gas events)
4 = RunTimePointDisable
5 = Point disabled by configuration
bits 3-4 - for HA use only
bit 5 -- maintenance fault exists
bit 6 -- monitor fault exists
bit 7 -- for HA use only