Modbus Point Maps - Honeywell H Series Installation Instructions Manual

Green class net meter
Table of Contents

Advertisement

H-SERIES GREEN CLASS NET METER

12.0 MODBUS POINT MAPS

Address
Reg Description
40001*
2
40003
2
40005
2
40007
2
* To clear single meter kWh/kVARh, set multiple points at 40001 for 8 points with data
set to 0000 0000 0000 0000 0000 0000 0000 0000. Jumper J6 must be closed.
Address
Reg Description
41001**
2
41003**
2
41005**
2
41007**
2
41009
2
41011
2
41013
2
41015
2
41017
2
41019
2
41021
2
41023
2
41025
2
41027
2
41029
2
41031
2
41033
2
41035
2
41037
2
41039
2
41041
2
62-0424-02
Modbus Integer Registers:
Energy delivered
Energy received
Reactive energy delivered
Reactive energy received
Modbus Float Registers:
Energy delivered
Energy received
Reactive energy delivered
Reactive energy received
Real power
Reactive power
Apparent power
Power factor
Current total
Current average
Voltage line-neutral
Voltage line-line
Frequency
Phase angle
Real power, phase A
Real power, phase B
Real power, phase C
Reactive power, phase A
Reactive power, phase B
Reactive power, phase C
Apparent power, phase A
42
Green
Net
Units
Meters
kWh Pulse
R/W
kWh Pulse
R/W
kVARh Pulse
R/W
kVARh Pulse
R/W
Green
Net
Units
Meters
kWh
R/W
kWh
R/W
kVARh
R/W
kVARh
R/W
kW
R
kVARh
R
kVARh
R
% PF
R
Amps
R
Amps
R
Volts-N
R
Volts-L
R
Hz
R
Degree
R
kW
R
kW
R
kW
R
kVAR
R
kVAR
R
kVAR
R
kVA
R