Honeywell Vertex M Technical Handbook page 210

Continuous gas monitor
Hide thumbs Also See for Vertex M:
Table of Contents

Advertisement

Vertex M
24-Point Continuous Monitor
TM
F1.1.
Obtain a computer with free RS232 serial port.
F1.2.
Start a terminal emulator program such as HyperTerminal
F1.3.
Configure the terminal emulator for 38400,N,8,1
F1.4.
Connect the provided DB9 cable from the selected port on the computer to the top DB9
connector on the Profibus card.
F1.5.
Take the SLC 5/03 PLC CPU out of run mode by turning the key briefly to "PROG" then back
to "REM". Verify that the RUN light is off. The Profibus card will not enter terminal mode if the
PLC is running.
F1.6.
Type asterisk ("
(DP, FDL)
F1.7.
Type
"locstn
F1.8.
Type
"baud
k,750k,1m5,3m,6m or 12m}.
F1.9.
Type "shownet" and verify that the communications parameters are as desired.
F1.10. Type
"slvtxlen 0 0
F1.11. Type "showslv" and verify that the communication parameters are as desired
F1.12. If additional information is desired type "help" and follow the instructions.
F1.13. Type "exit" to save the changes
F1.14. Put the SLC 5/03 PLC CPU into run mode by turning the key briefly to "RUN" then back to
"REM". Verify that the RUN light stays on.
Appendix A - Network Interface and Options
Table A-7. Procedure 1—Changing Profibus Configuration
*
") up to 20 times until the following message is displayed:
xx" where xx is the desired Profibus address.
yyy" where yyy is the desired baud rate from the set {9k6,19k2,93k75,187k5,500
zzz" where zzz is the desired memory size in words, usually 41 or 122.
F-13