3.6.8 Set Fault Relays

Fault relay contacts activate for instrument or
maintenance faults. Faults are associated with an entire
analyzer and not individual points.
Instrument faults indicate a loss of monitoring
on one or more points.
Maintenance faults indicate the Vertex M
System requires attention but is continuing to
monitor.
Note:
The number of relays used for fault indication is con-
figurable. See
Section 3.6.6 Configure
Defining an analyzer for association with a relay is a
four-step process:
1. Choose the relays to which you want to
associate with an analyzer.
2. Choose Instrument, Maintenance, Both or
None in the Change To... area.
3. Click the square representing the analyzer
or analyzers to associate with the relay.
The square changes color to indicate the
association.
4. Choose Accept to modify to the configuration
profile. Choosing Cancel leaves the alarm
definition unchanged.
Repeat for all relays.
To verify a relay's assignment to analyzers, choose the
contact. The associated analyzer changes color.
Section 3 - Startup
PLC.
3-32