Vertex M
24-Point Continuous Monitor
TM

4.6.5 Service

The Service Window provides a means to trigger the fault and alarm relays.
Create Fault Now
The Create Fault
N ow bu t t o n w i l l
only become visible
after an analyzer
and fault level are
selected. Touch the
button to generate
simulated fault.
Fault Test
Use the Fault Test to verify operation of fault relays.
Note:
The fault test simulates an actual fault condition and the Vertex M System activates fault relays. Notify appropriate
personnel that you plan to conduct a fault test.
To conduct a fault test:
1. Choose Main Screen, Menu, Service and then Fault Test.
2. Choose the analyzer for the fault test.
3. Choose either Instrument Fault or Maintenance Fault.
4. Choose Create Fault Now to activate the relay or relays connected to the selected analyzer and a fault
will appear in the event list.
5. To continue testing, repeat steps 2 through 4.
See
Section 4.5.4 Event List
Section 4 - Operation
to clear events.
4-44