Using the fieldbus for miscellaneous drive control requires:
Table 47: Fieldbus Controller Commands
Drive Parameter
1601
RUN ENABLE
1604
FAULT RESET SEL
1607
PARAM SAVE

Relay Output Control

Using the fieldbus for relay output control requires:
Table 48: Relay Output Control
Drive Parameter
1401
RELAY OUTPUT 1
1402
RELAY OUTPUT 2
1403
RELAY OUTPUT 3
1410
RELAY OUTPUT 4
1
1411
RELAY OUTPUT 5
1
1412
RELAY OUTPUT 6
1
0122
RO 1-3 STATUS
0123
RO 4-6 STATUS
1 . More than 3 relays requires the addition of a relay extension module .
NOTE: Note: Relay status feedback occurs without
configuration as defined below.

Analog Output Control

Using the fieldbus for analog output control (e.g. PID setpoint)
requires:
Table 49: Analog Output Control
Drive Parameter
1501
AO1 CONTENT SEL
0135
COMM VALUE 1
AO1 CONTENT MIN...
1502...1505
MAXIMUM AO1
1506
FILTER AO1
1507
AO2 CONTENT SEL
0136
COMM VALUE 2
AO2 CONTENT MIN...
1508...1511
MAXIMUM AO2
1512
FILTER AO2
OM 1191 • MD5 VFD
Value
7 (COMM)
8 (COMM)
1 (SAVE
Saves altered parameters to memory (then value returns to 0) .
Value
35 (COMM)
36 (COMM(-1))
Relay 1...3 status .
Relay 4...6 status .
Value
135 (COMM VALUE 1)
Analog Output 1 controlled by writing to parameter 0135 .
Set appropriate values .
136 (COMM VALUE 2)
Analog Output 2 controlled by writing to parameter 0136 .
Set appropriate values .
• Drive parameter values set as defined below.
• Fieldbus controller command(s) in the appropriate
location. (The location is defined by the Protocol
Reference, which is protocol dependent .)
Description
Run enable by fieldbus.
Fault reset by fieldbus.
• Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay
command(s) in the appropriate location . (The location
is defined by the Protocol Reference, which is protocol
dependent .)
Description
Relay Output 1 controlled by fieldbus.
Relay Output 2 controlled by fieldbus.
Relay Output 3 controlled by fieldbus.
Relay Output 4 controlled by fieldbus.
Relay Output 5 controlled by fieldbus.
Relay Output 6 controlled by fieldbus.
• Drive parameter values set as defined below.
• Fieldbus controller supplied analog value(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Description
Used for scaling
Filter time constant for AO1 .
Used for scaling
Filter time constant for AO2 .
70
f
a
ieldbUs
daPTer
Protocol Reference
Protocol Reference
Protocol Reference