Daikin MD5 Operation Manual page 77

Variable frequency drive controller
Table of Contents

Advertisement

Table 53 continued: Fault Listing
Fault Code
Fault Name In Panel
101
SERF CORRUPT
102
RESERVED
103
SERF MACRO
104
RESERVED
105
RESERVED
201
DSP T1 OVERLOAD
202
DSP T2 OVERLOAD
203
DSP T3 OVERLOAD
204
DSP STACK ERROR
205
RESERVED (obsolete)
206
OMIO ID ERROR
207
EFB LOAD ERR
1000
PAR HZRPM LIMITS
1001
PAR PFAREFNG
1002
RESERVED (Obsolete)
1003
PAR AI SCALE
1004
PAR AO SCALE
1005
PAR PCU 2
1006
EXT ROMISSING
1007
PAR FBUSMISSING
1008
PAR PFAWOSCALAR
1009
PAR PCU1
1010
PAR PFA OVERRIDE
1011
PAR OVERRIDE PARS
1012
PAR PFA IO 1
1013
PAR PFA IO 2
1014
PAR PFA IO 3
www .DaikinApplied .com
Description and Recommended Corrective Action
Error internal to the drive . Contact your local Daikin sales representative and report the error number .
Error in the system . Contact your local Daikin sales representative and report the error number .
Parameter values are inconsistent . Check for any of the following:
• 2001* MINIMUM SPEED > 2002* MAXIMUM SPEED .
• 2007* MINIMUM FREQ > 2008* MAXIMUM FREQ .
• 2001* MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (> 50)
• 2002* MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside proper range (> 50)
• 2007* MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (> 50)
• 2008* MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside proper range (> 50)
*These are factory set and tested . Contact your local Daikin sales representative if there is a problem .
Parameter values are inconsistent . Check for the following:
• 2007 MINIMUM FREQ is negative, when 8123 PFA ENABLE is active .
Parameter values are inconsistent . Check for any of the following:
• 1301* AI 1 MIN > 1302 AI 1 MAX .
• 1304* AI 2 MIN > 1305 AI 2 MAX .
*Not used with MicroTech III .
Parameter values are inconsistent . Check for any of the following:
• 1504* AO 1 MIN > 1505 AO 1 MAX .
• 1510* AO 2 MIN > 1511 AO 2 MAX .
*Not used with MicroTech III .
Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power . Check for
the following:
• 1 .1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1 .73 / P
• Where: P
= 1000 * 9909 MOTOR NOM POWER (if units are kW)
n
or P
= 746 * 9909 MOTOR NOM POWER (if units are HP, e .g . in US)
n
Parameter values are inconsistent . Check for the following:
• Extension relay module not connected and
• 1410...1412 RELAY OUTPUTS 4...6 have non-zero values .
Parameter values are inconsistent . Check for and correct:
• A parameter is set for fieldbus control (e.g. 1001 EXT1 COMMANDS = 10 (COMM)), but 9802 COMM PROT SEL =
0 .
Parameter values are inconsistent – 9904 MOTOR CTRL MODE must be = 3 (SCALAR: SPEED), when 8123 PFA
ENABLE is activated .
Parameter values for power control are inconsistent: Improper motor nominal frequency or speed . Check for both of the
following:
• 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16
• 0 .8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor Poles) < 0 .992
Both the override mode and PFA are activated at the same time . These modes are mutually incompatible, because PFA
interlocks cannot be observed in the override mode .
Override is enabled, but parameters are incompatible . Verify that 1701 is not zero, and (depending on 9904* value)
1702* or 1703* is not zero . *Not used with MicroTech III .
IO configuration is not complete – not enough relays are parameterized to PFA. Or, a conflict exists between Group 14,
parameter 8117*, NR OF AUX MOT, and parameter 8118*, AUTOCHNG INTERV . *Not used with MicroTech III .
IO configuration is not complete – the actual number of PFA motors (parameter 8127, MOTORS) does not match the
PFA motors in Group 14* and parameter 8118* AUTOCHNG INTERV . *Not used with MicroTech III .
IO configuration is not complete – the drive is unable to allocate a digital input (interlock) for each PFA motor
(parameters 8120* INTERLOCKS and 8127* MOTORS) . *Not used with MicroTech III .
77
d
iagnosTiCs
) < 3 .0
n
OM 1191 • MD5 VFD