Table 5 continued: Group 01: Operating Data
0118
DI 1-3 STATUS
Status of the three digital inputs .
• Status is displayed as a binary number .
• 1 indicates that the input is activated .
• 0 indicates that the input is deactivated .
0119
DI 4-6 STATUS
Status of the three digital inputs .
• See parameter 0118 DI 1-3 STATUS .
0120
AI 1
The relative value of analog input 1 in % .
0121
AI 2
The relative value of analog input 2 in % .
0122
RO 1-3 STATUS
Status of the three relay outputs .
• 1 indicates that the relay is energized .
• 0 indicates that the relay is de-energized .
0123
RO 4-6 STATUS
Status of the three relay outputs . Available if OREL-01 Relay Output Extension Module is installed .
• See parameter 0122 .
0124
AO 1
The analog output 1 value in milliamperes .
0125
AO 2
The analog output 2 value in milliamperes .
0126
PID 1 OUTPUT
The PID controller 1 output value in % .
0127
PID 2 OUTPUT
The PID controller 2 output value in % .
0128
PID 1 SETPNT
The PID 1 controller setpoint signal .
• Units and scale defined by PID parameters.
0129
PID 2 SETPNT
The PID 2 controller setpoint signal .
• Units and scale defined by PID parameters.
0130
PID 1 FBK
The PID 1 controller feedback signal .
• Units and scale defined by PID parameters.
OM 1191 • MD5 VFD
0 .0...100 .0%
0 .0...100 .0%
4006/4106
4007/4107
4006/4106
4007/4107
14
P
araMeTers
000...111
(0...7
1
decimal)
000...111
(0...7
1
decimal)
0 .1%
0 .1%
000...111
(0...7
1
decimal)
000...111
(0...7
1
decimal)
0 .0...20 .0
0 .1 mA
mA
0 .0...20 .0
0 .1 mA
mA
-1000 .0...
0 .1%
1000 .0%
-100 .0...
0 .1%
100 .0%
Unit and
scale
defined
by par .
and
Unit and
scale
defined by
par . 4206
and 4207
Unit and
scale
defined
by par .
and
www .DaikinApplied .com